Laserfiche WebLink
LIVE TEST DATA • <br /> Line Test Method Used: PTK-88 <br /> Test Date: <br /> 6-27-96 <br /> Tar* Number: 04-30-96 002-2-96 <br /> T2 12K 87 <br /> Product: Tl 12K 89 T3 12K 92 <br /> Unload 87 <br /> Pump type: Unload 89 USuper 92 <br /> Turbine <br /> Pump Make: Turbine Turbine <br /> Smith <br /> A.O. A.O. Smith <br /> Isolator: A.O. Smith <br /> Silver Bullet <br /> Line Material: Silver Bullet Suver Bullet <br /> Line Diameter (inches): Steel Steel Steel <br /> Test Pressure (psi): 2 2 2 <br /> Test Time (minutes): 50 50 50 <br /> Finish Pressure (psi): 10 10 10 <br /> Volume change (ml): 47 43 46 <br /> Volume change (GPH): 14 20 6 <br /> PASSIFAIL 0.022 .033 <br /> 0.010 <br /> PASS PASS <br /> PASS <br /> Line Test Comments: <br /> LEAK DEFECTOR DATA <br /> Test Method used: Red Jacket Approved AVO (Apparatus to Verify <br /> Operation) in accordance with EPA 40CFR280.44(a)per RJ-21 <br /> Test Date: <br /> Tank Number: 04-30-96 06-27-96 <br /> 04-30.96 <br /> Product: T7 12K 89 T2 12K 87 <br /> T3 12K 92 <br /> Unload 87 <br /> Manufacturer: Unload 89 Super 92 <br /> k <br /> Red Jacket Red Jacket Leak Detector Model: Red Jacket <br /> -036 <br /> Serial Number: Illegible 116 116-047 <br /> 209942432 <br /> Resiliency: Illegible 0224953475 <br /> Test Leak Rate (189 ml/mn = 3 gph): 150 100 100 <br /> Metering PSI: 3 gph 3 gph <br /> 3 gph <br /> Check Valve PSI: 14 13 11 <br /> Restricted Flow (Yes or No): 20 20 19 <br /> Yos YES <br /> PASS/FAIL: Yes <br /> PASS PASS <br /> PASS <br /> Leak Detector Comments: <br /> - omne ou evar wte <br /> oven<e, <br />