Laserfiche WebLink
CHAPTER 6.7, UNDERGROUND STORAGE OF HAZARDOUS SUBSTANCES <br /> underground storage tank installed after July 1, 1987, shall be equipped with <br /> secondary containment which complies with paragraphs (1) to (6), inclusive. <br /> (b) The underground tank system shall be designed and constructed with a monitoring <br /> system capable of detecting the entry of the hazardous substance stored in the primary <br /> containment into the secondary containment. <br /> (c) The underground storage tank shall be provided with equipment to prevent spills <br /> and overflows from the primary tank. <br /> (d) If different substances are stored in the same tank and in combination may cause a <br /> fire or explosion, or the production of flammable, toxic, or poisonous gas, or the <br /> deterioration of a primary or secondary container, those substances shall be separated <br /> in both the primary and secondary containment so as to avoid potential intermixing. <br /> (e) If water could enter into the secondary containment b <br /> Precipitation <br /> the facility shall contain a means of monitoring for water n rus onand forrremlovin'g the <br /> water by the owner or operator. This removal system shall also prevent uncontrolled <br /> removal of this water and provide for a means of analyzing the removed water for <br /> hazardous substance contamination and a means of disposing of the water, if so <br /> contaminated, at an authorized disposal facility. <br /> (f) Underground pressurized piping that conveys a hazardous substance shall be <br /> equipped with an automatic line leak detector and shall be tightness tested annually. <br /> (g) Before the underground storage tank is covered, enclosed, or placed in use, the <br /> standard installation testing for requirements for underground storage systems <br /> specified in Section 2-7 of the Flammable and Combustible Liquids Code, adopted by <br /> the National Fire Protection Association, (NFPA 30) as amended and published in the <br /> respective edition of the Uniform Fire Code, shall be followed. <br /> i (h) Before the underground storage tank is placed in service, the underground tank <br /> yyy� system shall be tested in operating condition using a tank integrity test. <br /> (i) If the underground storage tank is designed to maintain a water level in the <br /> secondary containment, the tank shall be equipped with a safe method of removing any <br /> excess water to a holding facility and the owner or operator shall inspect the holding <br /> facility monthly for the presence of excess water overflow. If excess water is present in <br /> the holding facility, the permitholder shall provide a means to analyze the water for <br /> hazardous substance contamination and a means to dispose of the water, if so <br /> contaminated, at an authorized disposal facility. <br /> (Formerly§ 25284, added by Stats.1983, C. 1046, § 3. Renumbered§ 25291 and <br /> amended by Stats. 1984, c. 1584, § 2; Stats.1985, c. 1228. § 3, eff. Se <br /> Stats. 1985, c. 1535 3 <br /> § , eff Oct. 2, 1985; Stats.1986, C. 248, § 151; Stats.�986, 5 <br /> c. 1025, § 2; Stats.1987, c. 1372, § 6; Stats.1989, c. 1397, § 11. Amended by <br /> Stats. 1996, c. 611 (S.B. 562), § 2.5.) h <br /> SWRC8 -- 25 <br /> it <br />