Laserfiche WebLink
ITISIntegrity Tank Testing Systev Inc. <br /> TEST DATA AND <br /> 'PEST RESULTS <br /> October 25, 1988 <br /> Mr. Ed Rocha PS92IN <br /> Ed Rocha Livestock AP <br /> 2973 Loomis Road R 2 7 1989 <br /> Stockton, California 95205 ENVIRONMENTAL HEALTH <br /> PERMIT/SERVICES <br /> Dear Mr. Rocha: <br /> Following is a summary Of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight . :according to the current <br /> rules , if the gain is less than .07 or the loss is less than . US <br /> gallops per one hour of testing . If the results are beyond these <br /> parameters , you should consider ta.k.ing some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 12, 000 Diesel -. 03148 Yes <br /> South 8, 000 <br /> manifolded <br /> iv'orthmest 2, 000 U/L Gas - . 0279 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> d260��j'z� <br /> W. Savage <br /> G�rtified 'Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />