Laserfiche WebLink
CAPACITY 10000 g PRECISIt UNDERGROUND TANK TESI'IN•ESULTS Patent. Pending <br /> TANK # Diesel PAGE 4 <br /> STAT # N/A TEST PROCEDURES <br /> TEST DATE: 11/15/01 Copyright 1985 <br /> NDE TECHNOLOOY, INC . PROPRIETARY <br /> 1 . (a) THE UNDERGROUND S'T'ORAGE TANK SYSTEM CERTIFIED TIGHT AT PRODUCT <br /> HEIGHT EQUAL TO THE GRADE LEVEL. Yes . <br /> (b ) Allowable leak resolution of instrumentation or allowable change <br /> per California Administrative Code Title 23 Waters , Chapter 3 <br /> Water Resources Control Board SubchapLer 16 Underground Storage <br /> Regulations , Part 2643 (b ) , Page 4 . 14; 0 . 05 gallons per hour. <br /> A:K* (c) MEASURED HOURLY CHANGE,' : LOSS (+ ) OR GAIN (-) GALLONS OR <br /> NUMERICAL LEAK RA'Z'E IS : +0 . 025 Gal/Hr. <br /> --- -------------------- ------------------------------ ------- <br /> This measurement is within the legal limits as defined in (b) . <br /> (See also computer plots or reduced data of leakage rate, Part. III) <br /> - Product .level Of the storage system at the time of testing: <br /> 2 . Total product level 130" <br /> 3 . Fill pipe height <br /> from bottom of tank 125'' <br /> 4 . Test pipe height <br /> from bottom of tank 145'' <br /> 5 . Grade level. <br /> from bottom of tank 121 '' <br /> 6. Tank top height from bottom of tank <br /> excluding piping, or tank diameter 94'' <br /> 7 . Test conduction -- <br /> total time <br /> Time leak rate calculated 2 . 52 Hours <br /> 8. Start 10 : 39 <br /> 9. End 13 : 32 <br /> (See also computer plots or reduced data of leakage rate , Part III <br /> (Calculated leak rate shall he based on data generated during the <br /> second hour of testing) <br /> Distance from grade level and/or locution at which the test was <br /> conducted ( tank top level , distance below grade level , distance <br /> above grade, etc. ) <br /> 10 . Distance from grade level to location <br /> test conducted: +gn <br /> 11 . Fluid level where the test was conducted . Test Stand <br /> 12. Does the tank show tho presence of vapor pockets? <br /> No <br /> If yes , was the owner informed of steps that must be taken to <br /> release all vapor Pockets in order to complete testing? <br /> Owners of storage tanks are under a legal obligation to report <br /> any leaking tanks to the agency having jurisdiction of the tank <br /> test. , <br /> NDE TECHNOLOGY, INC . PROPRIE ARY <br /> WATT INC . 3131 FAIRHAVEN DRIVE , BAKERSFIELD , CA 03308 (805) :322-9827 <br />