Laserfiche WebLink
CAPACITY 10000 g PRECISION UNDERGROUND TANK TESTING RESULTS Patent Pending <br /> TANK # Diesel PAGE 4 <br /> STAT # N/A TEST PROCEDURES <br /> TEST DATE : 12/01/89 Copyright 1985 <br /> NUE TECHNOLOGY, INC. PROPRIETARY <br /> 1 . ( a) THE UNDERGROUND STORAGE TANK SYSTEM CERTIFIED TIGHT AT PRODUCT <br /> HEIGHT EQUAL TO THE GRADE LEVEL. Yes . <br /> (b) Allowable leak resolution of instrumentation or allowable change <br /> per California Administrative Code Title 23 Waters , Chapter 3 <br /> Water Resources Control Board Subchapter 16 Underground Storage <br /> Regulations , Part 2643 (b) , Page 4 . 14 ; 0 . 05 gallons per hour. <br /> ** (c) MEASURED HOURLY CHANGE : LOSS (+ ) OR GAIN (-) GALLONS OR <br /> NUMERICAL LEAK RATE IS : +0 . 018 Gal/Hr . <br /> ------------------------------------------------------------------- <br /> This measurement is within the legal limits as defined in (b) . <br /> (See also computer plots or reduced data of leakage rate, Part III) <br /> Product level of the storage system at the time of testing: <br /> 2 . Total product level 142" <br /> 3 . Fill pipe height <br /> from bottom of tank 126" <br /> 4. Test pipe height <br /> from bottom of tank 156" <br /> 5 . Grade level <br /> from bottom of tank 134" <br /> 6. Tank top height from bottom of tank <br /> excluding piping, or tank diameter 96" <br /> 7 . Test conduction - <br /> total time <br /> Time leak rate calculated 2 : 12 Hours <br /> 8. Start 08: 13 <br /> 9. End 10 : 25 <br /> (See also computer plots or reduced data of leakage rate, Part III ) <br /> (Calculated leak rate shall be based on data generated during the <br /> second hour of testing) <br /> Distance from grade level and/or location at which the test was <br /> conducted ( tank top level , distance below grade level , distance <br /> above grade, etc. ) <br /> 10 . Distance from grade level to location <br /> test conducted: +B" <br /> 11 . Fluid level where the test was conducted. Test Stand <br /> 12 . Does the tank show the presence of vapor pockets? <br /> No <br /> If yes , was the owner informed of steps that must be taken to <br /> release all vapor pockets in order to complete testing? <br /> Owners of storage tanks are under a legal obligation to report <br /> any leaking tanks to the agency having jurisdiction of the tank <br /> test . <br /> NDE TECHNOLOGY, INC . PROPRIETARY <br /> WATT INC . 3131 FAIRHAVEN DRIVE , BAKERSFIELD , CA 93308 (805 ) 322-9827 <br />