Laserfiche WebLink
0 <br />Quality Petroleum Equipment <br />LDT - 890 Test Form <br />0 <br />RECEIVED <br />MAY 21 2015 <br />ENVIRONMENTAL <br />4CA'Tu nC0h0T#ACh1T <br />Test Information <br />Date: 4/09/2013 Test Company: Mid Valley Consulting & General Eng. <br />Telephone: 530-749.9892 Contact: James Day <br />Site ID FAST AND EASY Address: 10878 N. MWY 99 <br />City: STOCTON State: CA. <br />Type of Test Equipment: VMI LDT - 89OXAF <br />Submersible Pump Identification <br />MFG: RED JACKET Model No: P150S1 Serial No: 1061 <br />Leak Detector Identification <br />MFG: RED JACKET Model No: FXIV Serial No: 5381 <br />Replacement Leak Detector Identification <br />MFG Model No: Serial No <br />Line Conditions <br />1. Type of Pipe: FRP 2. Diameter of Pipe: 2" 3. Length of Pipe MY <br />4. Burial Depth of Leak Detector. 22" S. Kind of Fuel: 91 6. Date of Last Test: 201_2 <br />Test Conditions <br />1. Operating Pump Pressure: 28 PSI 2. Gallon per hour test rate: -3 —@10 psi <br />3. Static Line Pressure (Pump Off): 13 PSI 4. Bleed back Test (Pump Off): 65 nil <br />S. Step Through time to full flow 5 seconds (0 psi to full pump pressure, no lealk) <br />6. Leak detector stays in Leak Search Position with a 3 GPM leak -Yes: X PASS INo:_FAIL <br />7. Was the leak detector adjusted - Yes: No: <br />symptoms <br />1. Won't find 3 GPM leak.---,-,- 2. Stays in Slow <br />3. Other: <br />2 d dgb; 60 9 L LZ f 8 <br />