INVOICE IWC000033 TEST DATE: 03/29/95 <br /> UNDERGROUND TANK TESTERS <br /> 15870 AVENUE 288 <br /> VISALIA, CA 93292 <br /> 800-244-1921 <br /> f <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> B <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> CRISP TANK TESTING DELICATO VINEYARDS <br /> P.O. BOX 30487 12001 SOUTH HIGHWAY 99 <br /> STOCKTON, CA. MANTECA, CA. <br /> 95213 95336 <br /> CONTACT: LEONARD ,CRISP CONTACT: <br /> PHONE # : 209-931-1828 PHONE # : <br /> ***** COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br /> TANK $1 : REG UNLEADED TYPE: STEEL SN: .02 <br /> TANK IS TIGHT. <br /> TANK #2: DIESEL FUEL 2 TYPE: STEEL SN: .03 <br /> TANK IS TIGHT. <br /> WILLIAM E. COX <br /> OTIL UC 97-1583 - <br /> OPERATOR:U.S. TEST 1050-641 SIGNATURE: L�D ------ <br /> _----- --- DATE: <br />