RECEIVED <br /> DEC 2 3 2013 <br /> Reliable Petroleum Services, Inco ENVIRONMENTAL <br /> Page�®1 �DEPgRTMENT <br /> FLOAT SIZE: 2.0 IN. LEAK TEST METHOD <br /> L 8:DISP 15-16 <br /> WATER WARNING : 0.8 TEST ON DATE : ALL TANK TRI-STATE (SINGLE FLOAT) <br /> HIGH WATER LIMIT: 1 .0 JAN 29, 2009 CATEGORY : DISPENSER PAN <br /> MAX OR LABEL VOL: 10161 START TIME : DISABLED <br /> OVERFILL LIMIT 90/ TEST RATE :0.20 GAL/HR <br /> 9144 DURATION 2 HOURS <br /> L 9:DISP 13-14 <br /> HIGH PRODUCT 95/ TST EARLY STOP:DISABLED TRI-STATE (SINGLE FLOAT) <br /> 9653 CATEGORY : DISPENSER PAN <br /> DELIVERY LIMIT 15/ LEAK TEST REPORT FORMAT <br /> 1555 NORMAI. <br /> LOW PRODUCT 396 L10:87 ANNULAR <br /> LEAK ALARM LIMIT: 50 TRI-STATE (SINGLE FLOAT) <br /> SUDDEN LOSS LIMIT: 50 CATEGORY : ANNULAR SPACE <br /> TANK TILT 0.00 <br /> PROBE OFFSET 0.00 <br /> SIPHON MANIFOLDED TANKS 1.11 :87 TURBINE <br /> TRI-STATE (SINGLE FLOAT) <br /> TO: NONE CATEGORY : STP SUMP <br /> LINE MANIFOLDED TANKS <br /> TO: NONE LIQUID SENSOR SETUP <br /> - - - - - - - - - - - - L12:89 ANNULAR <br /> TRI <br /> SINGLE <br /> LEAK MIN PERIODIC: 50/ L I :DISP 5-6 CATEGORY-STATE <br /> : (ANNULARFSPACE <br /> 5184 TRI-STATE (SINGLE FLOAT) <br /> LEAK MIN ANNUAL 50/ CATEGORY : DISPENSER PAN <br /> 5184 L13:B9 FILL <br /> TRI-STATE (SINGLE FLOAT) <br /> L 2:DISP 3-4 CATEGORY : PIPING SUMP <br /> PERIODIC TEST TYPETRI-STATETRI-STATE (SINGLE FLOAT) <br /> CATEGORY : DISPENSER PAN <br /> ANNUAL TEST FAIL L14:89 TURBINE <br /> ALARM DISABLED TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : STP SUMP <br /> L 3:DISP 1-2 <br /> PERIODIC TEST FAIL TRI-STATE (SINGLE FLOAT) <br /> ALARM DISABLED CATEGORY : DISPENSER PAN L15:91 ANNULAR <br /> TRI-STATE (SINGLE FLOAT) <br /> GROSS TEST FAIL CATEGORY : ANNULAR SPACE <br /> ALARM DISABLED <br /> DISP <br /> ANN TEST AVERAGING: OFF L -STAT 11-12 <br /> PER TEST AVERAGING: OFF TRI-STAT (SINGLE FLOAT) <br /> CATEGORY : DISPENSER PAN L16:91 FILL <br /> TANK TEST NOTIFY: OFF TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : PIPING SUMP <br /> TNK TST SIPHON BREAKOFF L 5:DISP 9-10 <br /> TRI-STATE (SINGLE FLOAT) L17:91 TURBINE <br /> DELIVERY DELAY 15 MIN CATEGORY : DISPENSER PAN TRI-STATE (SINGLE FLOAT) <br /> PUMP THRESHOLD 10.00/ CATEGORY : STP SUMP <br /> L 6:DISP 7-8 <br /> TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : DISPENSER PAN <br /> L 7:DISP 17-18 <br /> TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : DISPENSER PAN <br />