02/13/2003 16:50 1*28094 SHIELD, HIRI.& CO, pggF 05 <br /> *OPW 61SO OVERFILL PREVENTION VALVES <br /> The OPW 5150 Overfill Prevention Valve is designed 10 prevent the overfill of underground <br /> storage tanks by providing a positive shut-off of product delivery.The shut-on valve is an integral <br /> pan of the drop hibe used for gravity filling.The OPW 6150 allows easy installation(without <br /> breaking concrete)and requires no special manholes. <br /> The OPW 6150 is a two-stage shut-off valve.When the liquid level rises 10 ebuu195%of lank <br /> rapacity, the valve mechanism is released,closing automatically will,the How. This reduces the <br /> now rale In approximately 5 qpm through a bypass valve. The Oparalor may then stop the filling <br /> Process and disconnect and drain the delivery hose.As long as the liquid exceeds the 95%level, <br /> the valve will close automatically each lime deliveryis attempted. <br /> If the delivery is not slopped and the liquid rises to about 98%of lank caoarily,the bypass <br /> valva closes completely.No additional liquid can flow into the lank until the level drops below a <br /> resel point, <br /> Models of the 6150 are available In meet virtually any UST application including two-point, <br /> coaxial,poopeled coaxial and remote fill. The 61SO-30W provides two-point ovefin protection for <br /> 3'riser pipes,and the 6150.1000 and 6150-100C(CARD)1e811"a grooved-tube design for use <br /> Willi lank gauging systems. Methanol and CARD(vnp(r-09111)approved models are also available, <br /> The OPW 6150 is approved by the New York City Fire Deparimenl.(Approval#4902) <br /> IMPORTANT <br /> — In older to prevent product spillage bran the Underground Storage Tank(UST),properly maintained delivery equipment and a proper <br /> connection at the lighl-fill adaptor are essenlial. Delivery personnel should be managed and trained In inspect delivery elbows and <br /> hoses for damaged and missing pans.They should always make certain there is a positive connection l ahvann the adaptor and <br /> elbow.If delivery equlpmant is rwl property maintained,of the elbow is not securely coupled to the adaptor,a serious spill may result <br /> when the OPW 6150 closes,causing a herard and environrireoful contamination. <br /> NOTE: The OPW 6150 is designed fur use on light-fill gravity drop applications only. Do not use for pressure fill applications. <br /> Features: <br /> • Simple,Easy and Quick Installation- ♦ No pressurization of The Tank- Certifications NY City Fire <br /> No excavation or special manholes Operates directly from liquid level. and Listings CARD Da ar tment <br /> required ♦Will Accept a Dipstick for Gauging. Ilse series Initial Approp vat _ <br /> • Economical- Costs a fraction of ♦ Retrofits,Directly•For both new and <br /> expensive,complicated and difficult cMr go p4sot <br /> to install valves. existing tanks with 7"or 4'fill risers. liner OctDcl oe <br /> • Furnished Complete-Supplild with • Quick Drain Feature-Automatically Updated Approval <br /> drains hose when head pressure Is Liner r91 a/ <br /> new upper and lower drop lubes, -- <br /> mounting hardware and thorough relieved. IISOM Approval <br /> Inslrucllons for quick job site lime. • Best Flow Rale in The Indushy.' ___,_ Letter 190.5 <br /> •ComplehtirAutomelite Operation•No AISOP Approval <br /> pr achecks to perform,no resets,and no Test wilnessed by Dowser-mom",Inc.,an ------ Letier,i li r <br /> overrides to be broken or abused independent laboratoryResults available <br /> upon request. <br /> Advantages of Overfill Prevention Materials <br /> Compared to Overfill Warill Systems <br /> Valve body:cast aluminum <br /> •Completely Automatic Operation- Speds fkl lve Operations - Float:While rubber,closed cell foam <br /> Does not rely on the alertness or speed Product flows unimpeded into the lank Valve:aluminum <br /> of response of the delivery attendant; until the hose`kick'that accompanies Seals:vilon <br /> for certainly of overfill prevention. the valve shut-on provides a clear Upper&lower Drop Tube:aluminum <br /> Keeps the Top of UST"Dry,"per signal Ilial the liquid has reached the Plastic parts:acetal <br /> EPA Requlremenls•Eliminating shut-of level, <br /> Possible leaks at loose bung filongs ♦ Simple and Inexpensive Installation• Hardware:stainless steel <br /> and the need hx double containment In both two-poinl and coaxial rill <br /> on van[lines, applications,no additional excavation, <br /> • Does Not Rely on Pressure in the manholes or van[piping aro required <br /> UST to Stop Flow-Allowing fester fill <br /> times and reducing spin risk. <br /> 1 <br />