Laserfiche WebLink
D. Results of Testing/Servicing <br /> Software Version Installed: <br /> complete the following checklist: <br /> Yes ❑ No* Is the audible alarm operational? <br /> VYes <br /> ❑ No' Is the visual alarm operational? <br /> ❑ No* Were all sensors visual) inspected, functional) tested, and confirmed operational? <br /> C2 No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> N/A operational? <br /> Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a-leak, fails to opQQQQraaa�te, or is electrically discon ected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) J�Sumparench Sensors;�ispenser Containment Sensors. <br /> Did you confirm positive shut-down due to eaks and sensor failure/di connection? Yes; ❑ No. <br /> ❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank ov rfill warning device (i.e. no <br /> N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fillpoint(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? % <br /> ❑ Yes* t No Was any monitoring equipment replaced? If yes, identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E, below. <br /> ❑ Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)❑ <br /> Product; ❑Water. If yes,describe causes in Section E,below. <br /> '671 Yes ❑ No* Was monitorings stem set-up reviewed to ensure proper settings?Attach set up re orfs,if applicable - <br /> Yes ❑ No* Is all monitoring equipment oerational Rer manufacturer's specifications? <br /> * n Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> Page 2 of 3 03101 <br />