SEPTEMBER 27, 2002 <br /> ■ ARCO FAC 6020 <br /> PETCON 1711 E YOSEMITE /HWY 99 <br /> TECHNOLOGIES MANTECA, CA <br /> INC. <br /> SCOPE OF WORK <br /> TO REPAIR THESE FAILED COMPONENTS <br /> 87, 89, 91 SECONDARY LINES <br /> 87 FILL SUMP <br /> 89 SPILL BUCKET <br /> 5/6, 7/8, 11/12, 13/14 DISPENSER PANS <br /> 14118 S.Inglewood Avenue 1. PERFORM HELIUM TEST TO LOCATE AND PINPOINT LEAK ON <br /> Hawthorne,CA 90250 SECONDARY LINES. <br /> a. TIGHTEN CLAMPS, RESEAT BOOTS. <br /> T 310 679 9991 b. IF NEEDED, EXCAVATE PORTION OF TANK SLAB AND <br /> F 310 679 9994 REPAIR PIPING PER MANUFACTURER'S <br /> RECOMMENDATIONS. <br /> c. IF NEEDED, REPLACE PENETRATION BOOTS ON <br /> DISPENSERS. <br /> ptimail@petcontech.com <br /> 2. REPAIR LEAKS IN FILL SUMP <br /> www.petcontech.com a. TIGHTEN CLAMPS, RESEAT BOOTS <br /> b. SEAL SUMPS COLLARS WITH FIBERGLASS AND RESIN. <br /> c. INSTALL SSI WEAVER PENETRATION FITTINGS WHERE <br /> PIPING / CONDUIT PASSES THROUGH SUMP WALL. <br /> 3. REPAIR SPILL BUCKET <br /> a. CLEAN / REPLACE DRAIN VALVES <br /> b. CLEAN / REPLACE GASKETS <br /> c. IF NEEDED, REPLACE SPILL BUCKETS TO MATCH <br /> EXISTING. <br /> 4. REPAIR UDCs <br /> a. TIGHTEN BOOTS <br /> b. REPLACE BOOTS IF TORN <br /> c. INSTALL SSI WEAVER PENETRATION FITTINGS WHERE <br /> PIPING / CONDUIT PASSES THROUGH DISPENSER PAN <br /> WALL. <br /> d. IF NEEDED, EXCAVATE PORTION OF TANK SLAB TO <br /> TIGHTEN / REPLACE UNDERGROUND PENETRATION <br /> BOOTS <br />