Laserfiche WebLink
.-� � _Test Dale: 01108/2004 <br /> "raWork Order: 2229753 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Type Tank or Disp Manufacturer Model or Diam./Wid01/Length Depth last Method Stan Initial Level Finish Final Pass/ <br /> If Material ( ) (�) Time Level Change Time Result Fail <br /> STP Sump REGULAR Owens Corning Fiberglass 44 62 Hydrostatic-Electronic 9:55 16 .00000 10:25 .000gph Pass <br /> STP Sump PLUS Owens Corning Fiberglass 44 62 Hydrostatic-Electronic 8:45 16 .00000 9:15 .000gph Pass <br /> STP Sump SUPREME Owens Corning Fiberglass 44 62 Hydrostatic-Electronic 8:40 16 .00004 9:10 .000gph Pass <br /> Dispenser Sump 1/2 Environ Plastic 42 35 Hydrostatic-Electronic 12:50 11 .00005 1:05 .0019ph Pass <br /> Dispenser Sump 314 Environ Plastic 42 35 Hydrostatic-Electronic 12:50 11 .00000 1:05 .000gph Pass <br /> Dispenser Sump 516 Environ Plastic 42 35. Hydroslatic-Electronic 12:00 11 .00342 12:15 .081gph Fail <br /> Dispenser Sump 718 Environ Plastic 42 35 Hydrostatic-Electronic 12:00 11 .00713 12:15 .169gph Fail <br /> Dispenser Sump 9/10 Environ Plastic 42 35 Hydrostalic-Electronic 11:20 11 .00008 11:35 .001gph Pass • <br /> Dispenser Sump 11112 Environ Plastic 42 35 Hydrostatic-Electronic 11:18 11 .00000 11:33 .000gph Pass <br /> • <br /> Comments: <br />