Laserfiche WebLink
2229 <br /> �� Test Date: 01/08/2004 <br /> 2229 <br /> Work Order. 75353 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Type Tank or Dlsp Manufacturer Model or DIam.NVidth/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material (") (") Time Level Change Time Result Fail <br /> STP Sump REGULAR Owens Coming Fiberglass 44 62 Hydrostatic-Electronic 9:55 16 .00000 10:25 .0009ph Pass <br /> STP Sump PLUS Owens Coming Fiberglass 44 62 Hydrostatic-Electronic 8:45 16 .00000 9:15 .000gph Pass <br /> STP Sump SUPREME Owens Coming Fiberglass 44 62 Hydrostatic-Electronic 8:40 16 .00004 9:10 .000gph Pass <br /> Dispenser Sump 112 Environ Plastic 42 35 Hydrostatic-Electronic 12:50 11 .00005 1:05 .001gph Pass <br /> Dispenser Sump 3/4 Environ Plastic 42 35 Hydrostatic-Electronic 1250 11 .00000 105 .000gph Pass <br /> Dispenser Sump 5/6 Environ Plastic 42 35 Hydrostatic-Electronic 12:00 11 .00342 12:15 .081 gph Fail <br /> Dispenser Sump 7/8 Environ Plastic 42 35 Hydroslatio-Electronic 12:00 11 .00713 12:15 .169gph Fail • <br /> Dispenser Sump 9/10 Environ Plastic 42 35 Hydrostatic-Electronic 11:20 11 .00008 11:35 .001gph Pass <br /> Dispenser Sump 11/12 J Environ Plastic 42 35 Hydrostatic-Electronic 11:18 11 .00000 11:33 .000gph Pass <br /> • <br /> Comments: <br />