a <br /> SWRCB,January 2002 It Page 2. <br /> 9. ILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes: ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested: 0 <br /> Test Method Developed By: Spill Bucket Manufacturer Industry Standard Professional Engineer <br /> Other(Spec) <br /> Test Method Used: ❑ Pressure Vacuum X❑ Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Spill Box# 87 Spill Box# 91 Spill Box# Spill Box# <br /> Bucket Diameter: 19 19 <br /> Bucket Depth: 12 12 <br /> Wait time between applying <br /> pressure/vacuum/water and 1 1 <br /> starting test: <br /> Test Start Time: 1500 1500 <br /> Initial Reading(Rl ): 9.5 8 <br /> Test End Time: 1600 1600 <br /> Final Reading(RF ): 9.5 9.5 <br /> Test Duration: 1 hr 1 hr <br /> Change in Reading(R F 0 0 <br /> Pass/Fail Threshold or ,� 0 <br /> Criteria: <br /> Test Result: X Pass 1:1 Fail Pass 0 Fail Pass [--] Fail Pass Fail <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />