Laserfiche WebLink
VAPOR FLOW METER OPERABILITY TEST <br /> Vapor flow meter serial number 14679 <br /> Dispenser fueling point numbers FP: 7 FP: <br /> Low grade V/L result #1 1.09 <br /> ISD A/L value #1 1.09 <br /> Difference between V/L result #1 and A/L value #1 (V/L—A/L) 0.00 <br /> Pass/ Fail (Pass = difference within ±0.15), if fail continue Pass <br /> Low grade V/L result #2 <br /> Low grade V/L result #3 <br /> Average of 3 V/L results <br /> ISD A/L value #2 <br /> ISD A/L value #3 <br /> Average of 3 ISD A/L results <br /> Difference between Average V/L and Average A/L values (Average V/L— <br /> Average A/L) <br /> Pass/ Fail (Pass = difference within ±0.15), if fail continue <br /> If fail, repeat steps for the second fueling point on the dispenser <br /> VAPOR FLOW METER OPERABILITY TEST <br /> Vapor flow meter serial number 35171 <br /> Dispenser fueling point numbers FP: 9 FP: <br /> Low grade V/L result #1 1.01 <br /> ISD A/L value #1 1.14 <br /> Difference between V/L result #1 and A/L value #1 (V/L—A/L) 0.13 <br /> Pass/ Fail (Pass = difference within ±0.15), if fail continue Pass <br /> Low grade V/L result #2 <br /> Low grade V/L result #3 <br /> Average of 3 V/L results <br /> ISD A/L value #2 <br /> ISD A/L value #3 <br /> Average of 3 ISD A/L results <br /> Difference between Average V/L and Average A/L values (Average V/L— <br /> Average A/L) <br /> Pass/ Fail (Pass = difference within ±0.15), if fail continue <br /> If fail, repeat steps for the second fueling point on the dispenser <br /> I declare, under penalty of perjury under the laws of the state of California that based on information and belief formed after <br /> reasonable inquiry, the statements and information provided in the document are true, accurate, and complete. <br /> Signature of <br /> Technician: Date: 3/19/2015 <br /> RE.C;E1VE;L <br /> WO: 2321928 MAY 0 4 2015 <br /> ENViRONMENTAI <br /> nr_pgpreare•— <br />