Laserfiche WebLink
IND.USTRIEs <br /> MARCH 4 , 198711 <br /> MAR 1 ? 1987 <br /> INC <br /> ENVIROMENTAL HEALT11 <br /> G E N E R A L SAFEWAY MEAT PLANT FERMIT/SERVICES <br /> ENGINEERING P .O. sox 8347 <br /> CONTRACTORS STOCKTON, CA 95208 <br /> & S E R V I C E <br /> S T A T 1 O N ATTENTION : JULIAN MUNOZ <br /> MAINTENANCE <br /> I_ICENSF NO. 467293 LOCATION : SAFEWAY MEAT PLANT <br /> 1111 Navy Drive , Stockton , CA 95206 <br /> RESULTS OF TANK TESTS PERFORMED JANUARY 19 , 1987 <br /> TANK #1 - 12 ,000 gallon diesel fuel tank - <br /> Full system test indicated a volume change <br /> of - . 021 gallons per hour under test <br /> conditions . <br /> Full system test within state guidelines . <br /> TANK #2 - 12 ,000 gallon diesel fuel tank - <br /> Full system test indicated a volume change <br /> of - . 019 gallons per hour under test <br /> conditions . <br /> Full system test within state guidelines . <br /> TANK #4 - 12 ,000 gallon diesel fuel tank - <br /> Full system test indicated a volume change <br /> of - . 031 gallons per hour under test <br /> conditions . <br /> Full system test within state guidelines . <br /> TANK #3 - was untestable due to a large loss of fuel <br /> prior to testing. Overnight the fuel level <br /> in the tank dropped approximately 6 inches . <br /> Further excavation is needed to discover the <br /> possible cause . <br /> PRECISION INDUSTRIES , INC . <br /> WARREN DEE FOWLES <br /> FIELD SUPERINTENDENT <br /> WDF/psw <br /> 2191 NAVY DR.,STOCKTON,CALIFORNIA 95206 209/462-9911 800/332-5900 <br /> I F, <br /> I Li <br /> I <br /> I <br /> S <br />