Laserfiche WebLink
°PIISION <br /> TRIES <br /> JULY 28 , 1986 <br /> INC. <br /> P. G. & E . <br /> G E N E R A L 1401 FU,-TON STREET <br /> ENGINEERING FRESNO, CA . ENVIROf%6ENTAL HEALTH <br /> CONTRACTORS FERMIT/SERVICES <br /> & S E R V I C E ATTENTION: MIKE BENNETT <br /> S T A T I O N <br /> MAINTENANCE RE : CONTRACT ZS-8645-006 <br /> LICENSE NO. 467293 PRECISION INDUSTRIES WORK ORDER NO. 263 <br /> LOCATION : 10901 E . •HWY 120, MANTECA , CA .. <br /> RESULTS OF TANK TEST PERFORMED JULY 8 , 1986 • <br /> TANK #1 - 1 ,000 gallon unleaded fuel tank - <br /> Full system test indicated a volume <br /> change of + . 010 gallons per hour under <br /> test conditions . <br /> Full system test within state guide- <br /> lines . <br /> PRECISION INDUSTRIES, INC. <br /> WARREN D. FOWLES <br /> FIELD SUPERINTENDENT <br /> WF/np <br /> 2191 NAVY DR.,STOCKTON,CALIFORNIA 95206 • 209/462-9911 • 800/332-5900 <br />