Laserfiche WebLink
MAN <br /> CALL PH E SUNNYVALE,TA DRIVE R <br /> �_iL, SUNALE,CA 94089 <br /> 400-0741 <br /> CONSTRUCTION INC, FAX)(408)400-0519 <br /> LICENSE#737351 EllM Eg1ppMENT INS <br /> August 21, 2006 <br /> THRIFTY OIL COMPANY# 172 <br /> 7647 PACIFIC AVE. <br /> STOCKTON, CA. <br /> SCOPE OF WORK. <br /> THE FOLLOWING IS THE COMPLETE SCOPE OF WORK TO BE PERFORMED DURING THE <br /> TEMPORARY CLOSURE OF THE THREE 12,000 UNDERGROUND FUEL STORAGE TANKS. <br /> Disconnect the electrical service to the submerged pumps. <br /> Remove the check valves from the submerged pumps . <br /> Purge lines using N20, product will return to the tanks. <br /> Remove the submerged pump extraction section. <br /> Rinse the tanks by applying pressurized water in the submerged pump riser. <br /> Remove the rinse water from the fill end of the tanks ( Asbury Environmental Services to <br /> complete this work) It is estimated that 500 gallons will be generated during this process. <br /> All hazardous manifest to be signed by the agent for Thrifty Oil. <br /> Reinstall the extractor units. <br /> • Cap off with locking caps all opening of the tank with the exception of the vent risers. <br /> • Mark electrical box for tag out. <br />