PUBLt HEALTH SEIVICES PQurN <br /> SAN JOAQUIN COUNTY : <br /> ENVIRONMENTAL HEALTH DIVISION �. { <br /> Ernest M. Fujimoto, M.D., M.F.H., Acting Health Officer <br /> 445 N. San Joaquin Street • P. O. Box 388 a Stockton, CA 95201-0388 [)F o R <br /> 209/468-3420 <br /> Date 5/6/95 f/1� <br /> TAIT and ASSOCIATES <br /> 2880 Sunrise Boulevard, Suite 206 <br /> Rancho Cordova, CA 95742 <br /> RE: Proposed retrofit at BP station 102479 7647 Pacific Ave. , <br /> Stockton CA <br /> 1. Overspill containment system must be 5 gallon minimum and <br /> UL listed. Provide information prior to plan approval. <br /> 2 . Piping that is to be used must declared prior to plan <br /> approval. <br /> 3 . Plans indicate that the dispenser pans will be filled with <br /> pea gravel. This is not an acceptable practise. All piping <br /> must be in plan view in the dispenser pan. <br /> 4 . Inorder to be in compliance with the 1998 upgrade <br /> requirements the tank system must have the following: <br /> a. Electronic shutoff of turbine if leak is detected or <br /> probe malfunctions. <br /> b. Overspill protection. <br /> c. Overfill protection. <br /> d. striker plates. <br /> 5. Plans fail to indicate the use of a ball extractor valve <br /> in the tank vent system. Ball extractor must be use on <br /> single walled vent pipe. <br /> 6. Flexible connectors used in dispenser pans and sumps not <br /> declared. Declare prior to plan approval. <br /> Ernest M. Fujimoto, M.D. , M.P.H. <br /> Acting Health Officer <br /> Robert McClellon R.E.H. S. <br /> Environmental Health Division <br /> A Division of San Joaquin County Health Care Services <br />