INSTALLATION NOTES: <br /> 1. THE INTRINSIC SAFE RELAYS GROUND CONNECTOR <br /> MUST BE WITHIN ONE OHM OF TRUE EARTH GROUND. USE <br /> A SEPARATE #8 AWG GREEN INSULATED COPPER WIRE TO <br /> BOUND BACKPAN. <br /> - 3/4' CONDUIT WITH 4#14 <2 ARE SPARE) <br /> TO 2, NO OTHER EQUIPMENT SHALL BE CONNECTED TO THE <br /> TO DAY TANK CONTROL PANEL INTRINSIC SAFE RELAYS GROUND. <br /> (E) 1/2' CONDUIT TO POWER <br /> MONITORING PANEL 3. CONDUCTORS ON THE HAZARDOUS SIDE TO THE BARRIER <br /> (E) 1/2' CONDUIT TO TO THE FIELD DEVICES MUST NOT BE CONNECTED <br /> OVERFILL ALARM THROUGH PLUGS, CABLES, TERMINAL BLOCKS OF OTHER <br /> VEEDER ROOT CONNECTING DEVICES WHICH CONTAIN NON-HAZARDOUS <br /> TLS-250i TANK BARRIER LOCATION WIRING. <br /> MONITOR CONSOLE TERMINALS (E) TELEPHONE JACK - e „ (E) 1/2' CONDUIT TO U.G. TANK <br /> 4. INTRINSICALLY SAFE WIRING MUST BE KEPT SEPARATE <br /> PROBE !{ 2 - (E) OUTLET & MODEM PLUG ��__ (N) 3/4' CONDUIT WITH 1#16 T,S.PR, TO FROM NON-INTRINSICALLY SAFE WIRING. <br /> DAY TANK CONTAINMENT SUMP SENSOR (LS-11) <br /> 4. 3 _1 5. INTRINSICALLY SAFE AND NON-INTRINSICALLY SAFE <br /> --- WIRING MAY OCCUPY THE SAME ENCLOSURE OR RACEWAY <br /> PROBE 2-E 4 __ — (E) ENCLOSURE CONTAINING <br /> PROBE 3{+ 5 --- -- OVERFILL_ ALARM RELAY IF THEY ARE AT LEAST 2 INCHES APART AND SEPARATELY <br /> _ <br /> I + 6 0 — (E) MODEM INSI➢E TLS-2501 CONSOLE ��_ i"-i & ENGINE OPERATION RELAY SECURED, INSIDE PANELS, FIELD WIRING TERMINALS FOR <br /> PROBE 4-E+ 8 0 (RECONNECT ENGINE OPERATIONINTRINSICALLY SAFE CIRCUITS MUST BE SEPARATED BY AT <br /> I RELAY TO NEW PUMP STARTERS LEAST 2 INCHES FROM NON-INTRINSICALLY SAFE TERMINALS, <br /> r0 1l PROBE 5{+ 100 ` LOCATED IN DAY TANK CONTROL OR BY A GROUNDED METAL PARTITION OR AN APPROVED <br /> Im 2 + 110 PANEL) INSULATING PARTITION. <br /> 8 3 PROBE 6-E e a <br /> _ (E) VEEDER ROUT 8. EXPLOSION PROOF JUNCTION BOXES WITH SEALS SHALL <br /> PROBE 7 +130 <br /> BE USED FOR INTRINSICALLY SAFE APPARATUS IN <br /> n IB 5 {+ 140 (E> RS-232 TLS-2501 TANK HAZARDOUS AREAS. <br /> 6 I PROBE 8{+150 MODEM CABLE MONITOR CONSOLE <br /> B 7 COMMON +160 <br /> 0 8 PRINT 7. AN APPROVED SEAL SHOULD BE USED AT THE POINT <br /> a 0 9 TRANSMIT (N) _> NEW WHERE THE INTRINSICALLY SAFE CONTROL CIRCUIT <br /> I G4C:i L.I. rlr �B 10 AUX RECEIVE (E) => EXISTING <br /> N <br /> 1011 RECEIVE MONITORING PANEL LAYOUT WIRING ENTERS ANY HAZARDOUS AREA. <br /> e L LB 12 +12 V DC NOT TO SCALE <br /> 25 nA MAX j 8. RACEWAYS, CABLE TRAYS AND OPEN WIRING FOR <br /> I - <br /> INTRINSICALLY <br /> IDENTIFIED WITH PERMANENTLYISHALL <br /> AFFIXED LABELS <br /> ALARM RELAY I 1 WITH THE WORDING "INTRINSIC SAFETY WIRING" OR <br /> --� 2 EQUIVALENT, THE LABELS SHALL BE SO LOCATED AS <br /> ALARM RELAY 21B3 __ A I TO BE VISIBLE AFTER INSTALLATION AND PLACED SO <br /> GNDI0 4 ' THAT THEY MAY BE READILY TRACED THROUGH THE <br /> F _____ BARRIEaA 5 INTRINSICALLY SAFE AREA ENTIRE LENGTH OF INSTALLATION. SPACING BETWEEN <br /> ,L GN LABELS SHALL NOT BE MORE THAN 25 FEET. <br /> 9. EACH CABLE LENGTH IN THE HAZARDOUS AREA MUST <br /> NOT EXCEED 1,000 FEET. <br /> EXISTING L <br /> #12 AWG <br /> 10. INSTALLATION OF INTRINSIC SAFE RELAYS, WIRING, <br /> - - --- --- -- - <br /> AND OTHER EQUIPMENT DETAILS MUST BE IN <br /> 120VAC 1Q FROM N ACCORDANCE WITH THE MANUFACTURER'S <br /> PANEL BOARD G - — --- --- - --- INSTRUCTIONS. DRAWINGS ARE PROVIDED ONLY AS <br /> TO BUILDING --- ------ -- - <br /> GROUND GRID SHIELDED GUIDELINES, NOT TO BE USED FOR CONSTRUCTION <br /> CABLE DETAILS. <br /> #12 AWG GND r ' — " ' — ' — "" — ' — ' — ' — ' ' 1 11. INSTALLATION SHALL BE PER THE NATIONAL ELECTRIC <br /> RELAY r_______. CODE. ARTICLE 504. <br /> I I TO (E) ❑VERFILL <br /> ENCLOSURE TO DAY TANK <br /> I ��- _— ALARM RELAY CONTROL PANEL 12. WIRING TO PROBES & SENSORS IN THE HAZARDOUS <br /> I _ 4'-- ISR-6 AREA MUST BE THW'N " GAS AND OIL RESISTANT" AND <br /> 26 /r E) ENGINE OPERATION RELAY ' DWG E-2 PLACED IN SEALED RIGID CONDUIT. <br /> TO DAY TANK � �_ _� (REPLACE IF COIL IS NOT 120 VAC) <br /> CONTROL PANEL N I_ , _ , _ , . . -„ _ , _ , _ , _ . _ . _ . _ . _ . _ . _ . . . . . J 13. CONDUITS LEAVING HAZARDOUS AREA SHALL BE <br /> DWG E-2 l - SEALED AT BOUNDARY BETWEEN HAZARDOUS & NON- <br /> NON-HAZARDOUS AREA MCN-HAZARDOUS AREA HAZARDOUS AREAS. <br /> -- "- - - - - - - - - - - -- - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - -- - - - - - - - - - - - - - - - - - - - - - ^ - - - - - - - - - - - - - - - - - - - - - - — — — — — — — — — — — — — — — — — — — <br /> 14. MINIMUM SIZE WIRING SHALL BE #14 AWG FOR SINGLE <br /> HAZARDOUS AREA HAZARDOUS AREA CONDUCTORS AND #18 FOR TWISTED SHIELDED PAIR (T.S.PR.) <br /> CABLES. SELECT WIRE OR CABLE AS RECOMMENDED BY THE <br /> EQUIPMENT MANUFACTURER AND APPROVED BY THE ENGINEER. <br /> 15. ALL CONDUITS SHALL BE RIGID GALVANIZED STEEL. <br /> 16. RUN CONDUITS OVERHEAD TO DAY TANK IN ENGINE ROOM. <br /> -------- ----y <br /> PROBE 1 i 17. INSTALL A PULLBOX AT END OF 4 EACH 90' <br /> sE>awR u- sBrscR u sErvscR u- BENDS IN ANY CONRUIT RUN. <br /> I i I I I I <br /> I <br /> I ESA Ii ESA i ESA i L -'� FS-1 <br /> MODULE i i MODULE 1 MODULE FLOW SWITCH <br /> ESUMP <br /> __J L—_____J L______J <br /> Irr-rrir-!L!�!IILS-12 LS-13EXPLOSION PROOF CAST TANK TANK FILLSUMP SENSORJUNCTION BOX SUMP SENSOR INSTALLATION PER(18 CUBIC INCH MINIMUM DETAIL "A" <br /> WITH 1J2" NPT THREADS) (TYP.) <br /> INSTALLATION PERDETAIL "A" ++ DAY TANK <br /> WEATHERPROOF CONNECTORS J-BOX TO SPLICE CORD (TYP')CORD TO SENSORFILL PIPECORD GRIP SEALS <br /> SUPPLIED WITH SENSORSEALING FITTINGLT-1 LS_-11 <br /> RIGID CONDUIT TANK LEVEL DAY TANK <br /> PROBE CONTAINMENT SENSOR NO. REVISIONS / AUTHORIZATIONS DATE BY <br /> �rl�r rrrr rrr�rrrnrr/ zzz-/_-zz rn <br /> LS-14 DFU'MNCS PREPMm FOR <br /> FROM J-BOX TO J-BOX <br /> UNDERGROUND <br /> RNSR PAcIFiC� " <br /> DETAIL "A" UNDERGROUND TANK INTERSTITIAL SEOCRNIEND. CAE. <br /> UNDERGROUND TANK REPLACEMENT <br /> STOCKTON MAIN <br /> 345 NORTH SAN JOAQUIN STREET STOCKTON, CA <br /> UE-042 SKTNCA01 <br /> FILE: 92046-13 �QQ,F S , DATE 7/1/93 DRAWN BY ZKV <br /> TLS -2501 UNDERGROUND TANK /T.F.Em hQ ; �u� NELMICN -� IENNEN pRO ECT ENGINEER CHECKED BY RLV <br /> �/ 3123 BROADWAY s N0. iW0 ENGINEERING AND ENVIRONMENTAL SERVICES EST/RO NO. UE17DIE SHEET B OF 10 SHEETS <br /> MONITORING SYSTEM STEM DIAGRAM SCA, g 8170 *f9j 3750 AUBURN BLVD., SUITE A, SACRAMENTO, CA 95827 R(ggq444���el / DRAW NG NUMBER E- 1 <br /> q <br /> (916) 457-6144 f� A (916) 485-7222 -:./� ��` /J/ ,�,"< Y-UE042-01 -9306 C,- I <br /> - RnANAGER <br />