Laserfiche WebLink
ITTSIntegrity Tank Testing Systems, Inc. <br /> June 7 , 1990 <br /> Mr. Jim Langston JUL 16 t$?J <br /> Langston' s ENVIRONMENT LHEALTH <br /> P. 0. Box 97 Site: 15615 SoPF'jgwj�CES <br /> Lathrop, California 95330 Lathrop, Cali o <br /> Dear Mr. Langston: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate <br /> governmental agency. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Center 4, 000 Reg Gas -.066 Beyond Parameter <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> ran <br /> Ke <br /> Certified T er <br />