ITTSIntegrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> June 20, 1989 <br /> Mr. Jim Langston <br /> Langston's Arco <br /> P. 0. Box 97 Site: 15615 South 7th Street <br /> Lathrop, California 95330 Lathrop, California <br /> Dear Mr. Langston: <br /> Following is a summary of the precision testing we recently conducted on <br /> your underground storage tanks) . <br /> Enclosed are copies of the test worksheets and computer generated data <br /> for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight, according to the current rules, if the <br /> loss or gain is less than .05 gallons per one hour of testing. If the results <br /> are be;fond these parameters, you should consider taking some remedial action. <br /> TANK #/ TANIK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Center 4,000 Reg Gas - .046 yeT"� pct t i <br /> North 4,000 Sup U/L Gas -.012 Yes <br /> Please contact us if you need additional assistance or information. <br /> Sincerely, <br /> rank Keser �+ <br /> Certified Te: r <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />