AB PRECISION ENVIRONMENTAL TESTING PROCEDURES <br /> CHEVRON USA SS#91918 <br /> 45 E. HARDING, STOCKTON, CA. <br /> DEALER: HENRY VAN DOW <br /> (209) 946-9136 <br /> TANK SYSTEM 13, 1000GAL WASTE OIL <br /> SITE CONDITION <br /> The test site located at 45 E. Harding, Stockton, CA. was left in the <br /> same condition that was present prior to the hydrostatic tank test. The <br /> tank was pumped out to enable the dealer to further use the tank for <br /> waste oil deposits. <br /> TANK TESTING <br /> As required by Chevron, the waste oil that was in the tank was pumped out <br /> and diesel #2 was replaced in order to run the Petro—Tite tank test. All <br /> coordinations of waste oil removal, product delivery and its transfer <br /> were handled by AB Precision Environmental. After the removal of the waste <br /> oil and the delivery of the testing fluids, a Petro—Tite tank tester was <br /> assembled and a hydrostatic tank test was performed in accordance with <br /> standard tank testing procedures. The final outcome for this tank resulted <br /> in a pass and met the NFPA 329 tank testing standard of t.05gph. Immediately <br /> after teh test was completed, teh tank was pumped dry to enable the <br /> dealer to use his tank. <br />