Laserfiche WebLink
TAIT <br /> a5.:x.iLl:ii CYlUSiIGGI I t"�}.; '4a;.a^ ^..:4;ti,Ar;�rir .Ga.42".YS <br /> i <br /> 1+x7141960181222 www ion r ao <br /> Test Date: 2015-11-25 <br /> LEAK DETECTOR TESTING <br /> Facility ID: 01 Client Name: JB Hunt <br /> Street Address: 2726 Loomis Rd. Technician: Victor Guerrero <br /> City: Stockton ICC#: 8017001-UT <br /> Zip Code/State: 95205 / CA Manufacturer Gert#: 2945 <br /> Test Information <br /> Product T1: Diesel <br /> Manufacturer Vaporless <br /> Model LD2000 <br /> New Leak Detector No <br /> Yes/No <br /> Serial Number 11061230 <br /> Electronic LD <br /> (Yes/No) No <br /> Calibrated Test Leak <br /> Rate: (189 mil/min Yes <br /> 10 PSI) (Yes/No <br /> Check Valve Holding <br /> PSI 40 psi <br /> Resiliency 100 MIL <br /> (Bleed Back MIL) p <br /> Slow Flow 19 psi = To <br /> Meterin PSI/ N/A <br /> Turbine Shut Down <br /> Electronic LD NA <br /> -- <br /> Yes/No/NA <br /> Slow Flow At Nozzle Yes <br /> Yes/No/NA <br /> Opening Time 3 Seconds <br /> (Seconds) <br /> Pass/Fail Pass <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The leak detector test pass/fail is determined using a low flow threshold trip <br /> rate of 3 gph at 10 PSI. <br /> Technician Signature: y&Avt 57�r Date: 2015-11-25 <br /> CAIVcA 588098!A[ IicM 0959941 NV hco 0049666 1 TX Ilc0 CR000004I <br />