ITTSOIntegrity Tank Testing Systa, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> May 18, 1989 <br /> Mr. John Pinasco <br /> Pinasco Plumbing 4 Heating SITE: ROBINSON TRUCKING <br /> P. 0. Box 55287 11180 S. Vallejo Court <br /> Stockton; California 95205 Stockton, California <br /> Dear Mr. Pinasco: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Enclosed are conies of test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the loss or gain is less than - 05 gallons per one hour <br /> of testing . If the results are beyond these Parameters , .you <br /> should consider taking some remedial action . <br /> TAI4K H/ 'TANK PRODUCT TI:S7' WITIII14 TIGHT <br /> LOCAT1014 CAPACITY CONTAINED RESULTS WANK PARAMETERS <br /> North of <br /> Shop 12,181 Diesel - .02358 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> .r j <br /> Frank Keser <br /> Certified :' s r - <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />