SHEETINDEK
<br /> Sheet No. Sheet Title t ; m �
<br /> 1 SITE PLAN V N
<br /> E01030600 FILL SUMP DETAILS
<br /> E01030600-A FILL/VAPOR RISER CALCULATIONS 5AN JOAQUIN COUNTY '� M
<br /> E01030600-8 FILL/VAPOR RISER STATIC ELECTRICITY PROTECTION ENVIRONMENTAL HEALTH DEPARTMENT \� N 00
<br /> E01031100 E ECTRSER MONTINMENTDDES E TAILORING AILS JOB SITE COPY ^ I"
<br /> E01031500 VEEDER ROOT SPECIFICATIONS ♦ c:)
<br /> E01031900 CONCRETE SLAB DETAILS
<br /> 1 r x
<br /> i i �°� � SCOPE OF WORK
<br /> LTH
<br /> SAN Ai HEA COU I"NT -o
<br /> " — - INSTALL NEW SPILL CONTAINMENT ON FILL AND VAPOR RISERS 3D4 EMU—ER AVETHI
<br /> ] �] �� ] I „w� °1'.� EXISTING VENT RISERS, TYR CA 95202
<br /> f 1 ( 1 - INSTALL NEW DISPENSER CONTAINMENT SUMPS 0 0
<br /> �n I I I I - INSTALL NEW FILL DROP TUBES WITH OVERFILL VALVE 1 CO
<br /> 1
<br /> 1 O 0 I - INSTALL NEW 36" FIBRELITE MANHOLE UDS 13 Appf0"d%10 dwKISS �R��y � �
<br /> ® I 18 $ I - INSTALL NEW SUMP— INSTALL NEW USENSOR TE PATAFILL ASUMP NK L� El ADD Ved. Us Rates p �
<br /> I - PATCH A.C. PAVING AND CONCRETE AS REQUIRED RReemarksDDro 0
<br /> GENERAL NOTES -----'r' :z
<br /> g (�j�
<br /> pg ® I I �] �� ] I I S " 1. ALL WORK SHALL BE IN ACCORDANCE WITH THE CURRENT APPLICABLE EDIPdI �,� I �y alt's Z
<br /> 3I : a UNIFORM PLUMBING CODE, UNIFORM MECHANICAL CODE, UNIFORM FIRE CODEAMP1�1J a18 QS96W�Atju
<br /> 1 I � k
<br /> � _ p h CONSTRUCTION SAFETY ORDERS, AND ALL OTHER APPLICABLE STATE, CITY ANDSWiM$5R1( ((NgE5lits of state laws rtocal ordinances.
<br /> 9 p 2. CONTRACTOR SHALL DETERMINE THE LOCATION AND DEPTH OF ALL BURIED PIPES AND UTILITIES, WHETHER SHOWN V d
<br /> OR NOT SHOWN ON THESE PLANS, PRIOR TO THE START OF CONSTRUCTION. NOTIFY UNDERGROUND SERVICE ALERT
<br /> el I Y 1-800-227-2600, AT LEAST TWO WORKING DAYS PRIOR TO THE START OF CONSTRUCTION.
<br /> 3. CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS PRIOR THE START OF CONSTRUCTION.
<br /> it II (34. SITE SPECIFIC ARCHITECTURAL AND CIVIL DRAWINGS SHALL TAKE PRECEDENCE FOR REFERENCING ALL DIMENSIONS,
<br /> L I I ELEVATIONS AND EQUIPMENT LOCATIONS.
<br /> 5. ALL DIMENSIONS AND CONDITIONS SHALL BE CHECKED AND VERIFIED IN THE FIELD BEFORE STARTING ANY WORK,
<br /> ANY DISCREPANCIES :SHALL BE CALLED TO THE ATTENTAN OF THE OWNER'S REPRESENTATIVE FOR HIS DECISION PRIOR
<br /> 1 l7; �❑ I \ ^,rw I \ ,.r I PROCEEDING WITHTHE WORK.
<br /> SHA
<br /> 6. CONTRACTOR SHALL COORDINATE AND OBTAIN ALL REQUIRED TESTS, INSPECTIONS AND SIGN-OFFS AS REQUIRED BY
<br /> 1 9 MANUFACTURER'S SPECIFICATIONS AND LOCAL REGULAT'ONS PRIOR TO BEING PLACED INTO OPERATION. PROVIDE COPIES
<br /> _ OF TEST RESULTS TO OWNER AND REGULATORY AUTHORITIES.
<br /> i -[ PRESSURE VACUUM VENT 7. ALL TANK AND DISPENSER SUMPS SHALL BE HYDROSTATICALLY TESTED (LAKE TEST) WITH STANDING WATER TO INSURE
<br /> REFER TO ENLARGED PARTIAL PLAN BELOW THAT THE SUMPS ARE WATERTIGHT IN ACCORDANCE WITH OWNER'S AND REGULATORY AGENCY REQUIREMENTS.
<br /> 1 [� N.T.S. 8. ALL TANK AND PIPING SYSTEMS, LEAK DETECTORS AND MONITORING SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH
<br /> STATE, COUNTY, CITY AND OTHER LOCAL CODES AND REGULATIONS. CONTRACTOR SHALL GIVE REGULATORY AUTHORITY
<br /> ■ •d'u�w a+� AND OWNER'S REPRESENTATIVE 48 HOURS ADVANCE NOTICE OF AND TESTING OR INSPECTIONS.
<br /> 9. CONTRACTOR SHALL PROTECT ALL EXISTING FACILITIES, BOTH PUBLIC AND PRIVATE, WHICH ARE TO REMAIN UNLESS z
<br /> NOTED OTHERWISE. CONTRACTOR SHALL REPAIR OR REPLACE, TO THE OWNER'S SATISFACTION, ANY EXISTING FACILITIES
<br /> WHICH ARE DAMAGED AS RESULT OF CONTRACTOR'S OPERATIONS.
<br /> SITE PLAN 1N RAMP - INTERSTATE 205 — N 10. ALL TRENCHES IN TRAFFIC AREAS, INCLUDING PEDESTRIAN TRAFFIC AREAS, SHALL BE COVERED WITH TRAFFIC RATED
<br /> PLATES WHEN WORK IS NOT IN PROGRESS.
<br /> SCALE: i"= 20'-0" 11. ALL WORK AREAS SHALL BE ADEQUATELY BARRICADED THROUGHOUT THE CONSTRUCTION PERIOD.
<br /> 12. EDGES OF EXISTING PAVEMENT, CONCRETE SLABS, CONCRETE CURBS AND SIDEWALKS SHALL BE NEATLY TRIMMED z
<br /> PRIOR TO PATCHING, CONTRACTOR SHALL SAWCUT EXISTING PAVEMENT, SLABS, ETC IN NEAT STRAIGHT ONES. 9
<br /> 13. CONTRACTOR SHALL REPLACE TANK RISERS AS REQUIRED, PER SHELL ENGINEERS DIRECTION.
<br /> — — — — — — — — — — — 14. WHEN BONDING A NEW SUMP COLLAR TO EXISTING SINGLE WALL TANKS, A NITROGEN BLANKET SHALL BE USED
<br /> 24'-0" PER TANK MANUFACTURERS SPECIFICATIONS. ym
<br /> EXISTING/NEW TANK SLAB 15. CONTRACTOR SHALL REPLACE MISCELLANEOUS BOXES EQUIVALENT TO EXISTING. MONITORING WELLS NEED WATERTIGHT BOXES.
<br /> 16. CONTRACTOR SHALL BE RESPONSIBLE FOR ADDITIONAL CAVE-IN AT TANK EXCAVATION, BEYOND WHAT IS INDICATED ON THE
<br /> N O N G SPECIFICATIONS.
<br /> 0
<br /> I _ _ NOTES
<br /> r r �L_l f PREMIUMI. DIESEL 2
<br /> L— TW _ L — — IBJ J / 12 K 1 ( 12 K \ O SAWCUT EXISTING TANK SLAB TO EXPOSE TANK TOP Al FILL/VAPOR RISERS
<br /> UU I I I IINSTALL NEW NON-DISCRIMINATING SUMP SENSOR, (TYP. OF 4) REFER TO
<br /> I I © SHEET #EC1031400 FOR INSTALLATION DETAILS (SIM.) L.iJ
<br /> P P fm
<br /> INSTALL NEW 4"0 BLACK STEEL FILL RISER AND NEW 4"0 BLACK STEEL OFFSET VAPOR RISER, Q
<br /> (TYP.) REFER TO SHEET #E01030600 FOR INSTALLATION DETAILS 0::
<br /> ,L. snP I I. 0 I C.7
<br /> O © NOT USED
<br /> I I I I I
<br /> I I I I
<br /> 0 TLM O INSTALL NEW FILL DROP TUBE WITH OVERFILL PROTECTION VALVE SET AT 95% OF TANK CAPACITY
<br /> L FOR POSITIVE SHUT-OFF, REFER TO EQUIPMENT LIST ON THIS SHEET FOR MAKE AND MODEL NUMBER (TYP.) Z
<br /> INSTALL NEW SPILL CONTAINMENT FILL AND VAPOR RISERS, REFER TO EQUIPMENT W
<br /> I O LIST ON THIS SHEET FOR MAKE AND
<br /> MODEL NUMBERS (TYP.) Z
<br /> © INSTALL NEW FIBRELITE EMS90 48"0 SUMP BONDED ONTO NEW 48"0 TANK COLLAR, Q
<br /> (TYP. OF 4) REFER TO SHEET #E01030600 FOR INSTALLATION DETAILS 1---
<br /> I Z
<br /> REINFORCE CONCRETE SLAB AROUND MANHOLE W/ 3-#4 REBAR 8' 0
<br /> B C E IF I I 1 1 O IN LENGTH 9"O.C.. PLACE REBAR 6" FROM SIDES OF BOX. MIN. 2" COVER (�
<br /> G H M I c)
<br /> P PO O REPLACE EXISTING TANK SLAB, AS INDICATED ON TANK SLAB PLAN, WITH NEW B" REINFORCED CONCRETE.,
<br /> I . I REFER TO DRAWING 001031900 LLJ L/•7
<br /> _ — — INSTALL PRESSURE/VACUUM VENT VALVE ON TANK VENT RISERS (TYP. OF 4), INSTALL W Z U >
<br /> r —1 "\ / \ ! ccgg O PERMANENT YELLOW OR GOLD LABEL WITH BLACK LETTERING STATING THE —U
<br /> L _ 44POSITIVE AND NEGATIVE PRESSURE SETTINGS SPECIFIED BELOW: EL
<br /> POSITIVE PRESSURE SETTING: 3.0 f 0.5 INCHES H2O N 0 m
<br /> .1 LEGEND NEGATIVE PRESSURE SETTING: 8.0 t 2.0 INCHES H2O
<br /> N O N O EXISTING TO REMAIN Q INSTALL NEW 36"0 FIBRELITE MANHOLE UD (TYP. OF 18) ¢" IL U
<br /> EXISTING TO BE REMOVEDJ --j
<br /> Q Q
<br /> O �\ © INSTALL NEW 3/4"0 CONDUIT FROM THE NEAREST MONITORING J-BOX, TO NEW SUMP AT FILLS, (TYP. OF 4), J
<br /> NEW CONSTRUCTION
<br /> o 1 ® 1 EXTENT OF CONSTRUCTION O INSTALL STATIC GROUNDING ON ALL TANK RISERS, REFER TO DRAWING E01030600-B W 1"�' —J
<br /> H F- wN ¢
<br /> A O SAWCUT EXISTING ISLAND AS REQUIRED TO REMOVE EXISTING UNDER DISPENSER CONTAINMENT SUMPSr^ = N M
<br /> ' RE-INSTALL EXISTING DISPENSERS ON EXISTING ISLANDS, WITH NEW UNDERDISPENSER CONTAINMENT V J
<br /> O SUMPS (TYP. OF 6). INSTALL BEI NON-DISCRIMINATING SUMP SENSOR. REFER TO SHEET #E01031100 FOR
<br /> INSTALLATION DETAILS. DRAWN BY: JLR
<br /> rus nM © EXISTING SPANNER CABINET, (TYP. OF 6) DATE:WED BY: JLR
<br /> EQUIPMENT LIST JOB NO: 12156.1
<br /> I � I
<br /> N 0 N O NO EQUIPMENT DESCRIPTION MANUFACTURER MODEL QUANTITY SUPBPrLIED NOTES DEC 13 2 �
<br /> s P s 0 UNDERGROUND STORAGE TANK EXISTING DOUBLEWALL EXISTING TANK BURY
<br /> DEPTH IS 4'-0"t
<br /> ROTATABLE ADAPTER (FILL) OPW 61SALP-EVR DIST.
<br /> Q3 4" DUST CAP (FILL) OPW 634TT-EVR DIST.
<br /> ® SPILL CONTAINMENT BUCKET (FILL) OPW/POMECO 1-2100 SERIES DIST.
<br /> P P I REGULAR f IPLLUS 0 PRESSURE/VACUUM VENT VALVE HUSKY 4885 (2" THREADED) DIST.
<br /> 212
<br /> © 4" DROP TUBE OPW 6150-EVR (W/ OPD) DIST.
<br /> ' O7 ROTATABLE ADAPTER (VAPOR) OPW 81VSA-LVR DISL
<br /> L — — — — — — — — — — — — — — ® 4" DUST CAP (VAPOR) OPW 17117-EVR DIST, SHEET
<br /> Q SPILL CONTAINMENT BUCKET (VAPOR) OPW/POMECO 1-2100 SERIES DIST.
<br /> 36"0 MANHOLE LID FIBRELITE FL36 DIST 1
<br /> ENLARGEDPARTIAL PLAN 11 4" EXTRACTOR FITTING OPW 233 DIST. VAPOR RISER
<br /> SCALE: 1/8"= V-0" {12 48"0 SUMP W/ 42"0 TANK COLLAR FlBREUTE EM590 DIST.
<br /> \.:/ DISPENSER CONTAINMENT SUMP BEI FACTORY ASSEMBLED SHELL OF 8 SHEETS