Laserfiche WebLink
-- - -- -- - <br /> - - - - - - - - --- - - - - - <br /> — 100 OHMS MAXIMUM <br /> 2 POINT GROUND-EARTH -.- <br /> UNDERGROUND \ RESISTANCE <br /> STORAGE TANK \ COMPOSITE ASSEMBLY - <br /> - METAL ASSEMBLY TESTING : NOTES: <br /> \ CAUTION: AVOID CONNECTING ANY ELECTRICAL TEST ALL STAGE I FILL AND VAPOR RISER ADAPTERS SHALL BE <br /> LEAD TO THE FILL OR ELECTRICALLY GROUNDED TO PROMOTE THE <br /> ,I BONDING l GROUND T' THAT WOULD POTENTIALLY PRODUCESTATIC ER RELAXATION OF STATIC CHARGE. <br /> CONNECTOR INDEPENDENT <br /> JUMPER GROUND DISCHARGE OR SPARKS OF ANY KIND. HIGH RESISTANCE OR NON-CONDUCTIVE FLUID FLOWING <br /> 100K OHMS THE FILL AND VAPOR RISERS SHALL BE TESTED THOUGH PIPING CAN GENERATE STATIC CHARGES 'I <br /> SUMP MAX. AFTER INSTALLATION AND PERIODICALLY TO VERIFY <br /> CAPABLE OF IGNITING FUEL VAPORS. PROPER BONDING <br /> BONDING AND GROUNDING COMPETENCY, AND GROUNDING OF THE FILL AND VAPOR RISER <br /> / THE MAXIMUM RESISTANCE FROM ANY FILL OR ASSEMBLIES ARE NECESSARY To ASSURE SAFE FILLING <br /> OPERATIONS <br /> VAPOR ADAPTER TO THE BODY OF THE GROUND <br /> ROD SHALL NOT EXCEED 10 OHMS FOR A THE BONDING AND GROUNDING FOR STATIC ELECTRICITY <br /> METALLIC RISER PIPE, SPILL CONTAINMENT AND PROTECTION SHALL BE IN COMPLIANCE PER ALL <br /> ADAPTER ASSEMBLIES. <br /> _ APPLICABLE FEDERAL, STATE AND LOCAL CODES <br /> INCLUDING NFPA 30, FLAMMABLE AND COMBUSTIBLE <br /> UNDERGROUND THE RESISTANCE THROUGH ANY COMPOSITE OR LIQUIDS CODE, NFPA 77, RECOMMENDED PRACTICE ON <br /> STORAGE TANK \ NONMETALLIC STAGE I CONTAINMENT FITTING SHALT_ STATIC ELECTRICITY, NFPA 70, NATIONAL ELECTRIC CODE, <br /> \ TESTING BURIED GROUND ROD SYSTEM (ETG. SITES) BE MEASURED WITH A OHMMETER CAPABLE OF AND THECALIFORNIA CODE OF REGULATIONS, <br /> READING UP TO 10 MEGAOHMS. PER THE SHELL SUBCHAPTER 15, PETROLEUM SAFETY ORDERS-REFINING, <br /> GROUND STANDARD, THE SUM COLLECTIVE RESISTANCE OF TRANSPORTATION AND HANDLING, ARTICLE 5, FIRE AND <br /> THESE SEMI-CONDUCTIVE ELEMENTS SHALL NOT EXPLOSIONS, <br /> BONDING CONNECTOR EXCEED 100,000 OHMS. FOR THESE SYSTEMS, <br /> JUMPER THE GROUND RESISTANCE TESTER MUST BE <br /> CONNECTED TO THE GROUND CONDUCTOR PER SECTION N THE R UNDFPA 77, THE MEASURED TOTAL <br /> / 10 OHMS CONNECTION ON THE COMPOSITE CONTAINMENT RESISTANCE M THE GROUND PATH ON EARTH SHALL BE <br /> SUMP SYSTEM OR RISER PIPE, LESS THAN 1 MEGAOHM WHICH IS CONSIDEREDi, <br /> / MAX. ADEQUATE FOR RELAXATION OF STATIC CHARGE. THE <br /> COMPOSITE ASSEMBLY TEST LEAD CONNECTED MAXIMUM ALLOWABLE GROUND PATH TO EARTH <br /> FOR INSTALLATIONS WITHOUT AN EXPOSED GROUND <br /> TO GROUND ROD RESISTANCE FOR STATIC ELECTRICITY GROUNDING <br /> METAL ASSEMBLY ROD CONNECTION, TOTAL SYSTEM RESISTANCE APPLICATIONS FOR SHELL OIL PRODUCTS US STATION <br /> (NOT LUG OR WIRING) SHALL BE MEASURED WITH A GROUND RESISTANCE SITES SHALL NOT EXCEED 100,000 OHMS. <br /> - TESTER BY A QUALIFIED ELECTRICIAN FAMILIAR WITH <br /> ----� GROUND TESTING. THE TWO POINT METHOD MAY PER SECTION 6.4.1.3 OF NFPA 77, THE RESISTANCE IN <br /> BE USED WITH THE SITE ELECTRICAL GROUNDING METALLIC BONDING AND OR GROUNDING SYSTEMS SHALL <br /> UNDERGROUND \ AS THE SECOND TEST POINT. BE LESS THAN 10 OHMS. RESISTANCE HIGHER THAN 10 <br /> STORAGE TANK \ 10 K OHMS OHMS INDICATES INADEQUATE CONNECTIONS. <br /> THE NEC MAXIMUM GROUND PATH RESISTANCE FOR <br /> MAX. CURRENT CARRYING APPLICATIONS IS 25 OHMS, <br /> HOWEVER, GROUND ROD TO EARTH RESISTANCE UP A GROUNDING SYSTEM PER NEC CODE FOR CURRENT <br /> TO 100 OHMS SHALL BE ACCEPTABLE PER THE CARRYING CONDUCTORS SHALL BE CONSIDERED MORE <br /> BONDING GROUND THAN ADEQUATE FOR A STATIC ELECTRICITY GROUNDING <br /> JUMPER CONNECTOR SHELL STANDARD FOR STATIC ELECTRICITY SYSTEM. <br /> - PROTECTION OF THE FILL AND VAPOR RISERS. <br /> PER THE NFPA 30, SECTION 5-6,3.4 ALL PARTS OF THE FILL <br /> SUMP PIPE ASSEMBLY, INCLUDING THE DROP TUBE, SHALL <br /> FORM A CONTINUOUS ELECTRICALLY CONDUCTIVE PATH. <br /> SIZINTESTING EXPOSED GROUND ROD SYSTEM CONN CTOROF EFOR STATIC <br /> ANDBONDING <br /> SYSTEMS <br /> WIRE <br /> BACKFILL _ CONDUCTORS FOR STA"TIC PROTECTION SYSTEMS IS <br /> NATIVE SOIL TYPICALLY BASED ON MECHANICAL STRENGTH RATHER <br /> THAN CURRENT CARRYING CAPACITY. HOWEVER, PER <br /> THE CALIFORNIA CODE OF REGULATIONS, THE MINIMUM <br /> PLAN VIEW 1 GROUND WIRE SIZE FOR BONDING AND GROUNDING SHALL BE <br /> O ACCESS EXTREME CAUTION MUST BE OBSERVED WHILE USING ANY NON-INTRINSICALLY <br /> ROD DOVER f :SAFE DEVICE IN CLASSIFIED AREAS. SUMP MUST BE TESTED FOR VOLATILE i COPPER AWG #8 <br /> ■ 'VAPORS PRIOR TO USE. ELECTRICAL CONNECT MUST BE MADE WITH JUMPER ■ A 5i8"0 13Y 10' LONG COPPER CLAD STEEL GROUND ROD <br /> 'WIRE SO FINAL CONNECTION IS AWAY FROM CLASSIFIED AREAS, SHALL BE DRIVEN INTO NATIVE SOIL ONLY. PLACING THE <br /> GROUND ROD INTO TANK PIT PEA GRAVEL SHALL NOT BE <br /> PERMITTED UNDER ANY CONDITIONS, THE CONTRACTOR <br /> IS RESPONSIBLE FOR CLEARING ANY UNDERGROUND <br /> UTILITIES PRIOR TO INSTALLATION OF THE GROUND, <br /> ® GROUND ROD CLAMP 8" H-20 O THE GROUND ROD TO GROUND WIRE CONNECTION SHALL <br /> ACCESS COVER MATERIAL LIST <br /> CORD GRIP © METAL BE ACCESSIBLE THROUGH A D RATED 8"O MINIMUM <br /> COMPOSITE CONTAINMENT CORD GRIP SLOPE CONCRETE ACCESS COVER TO ASSIST INSPECTION, MAINTENANCE <br /> CONTAINMENT ASSEMBLY AND "TESTING. THE SCREW TYPE GROUND ROD CLAMP <br /> ELBOW SHOWN O / EX ELBOW 10 5/8"0 X 10' LONG COPPER CLAD STEEL SHALL BE UL LISTED FOR DIRECT BURIAL. <br /> ASSEMBLY /t/ 1i Cia ?,.,r <br /> ROTATED 90 , Y i` GROUND ROD; GLAVEN INDUSTRIES <br /> P/N 6260613 or EQUIVILENT ONE STRANDED #8 THHN CONDUCTOR SHALL BE RUN TO <br /> CONDUCTOR Bg EACH FU_L AND VAPOR RISER CLUSTER FROM THE <br /> a CONDUIT 6 GROUND ROD. THE CONDUCTOR SHALL HAVE 18" <br /> �I \ CORD ® GROUND ROD CLAMP, Ul. LISTED FOR <br /> MINIMUM COVER. THE CONDUCTOR SHALL PENETRATE <br /> GRIP DIRECT BURIAL; THOMAS-BETTS THE SUMP USING A APPROVED ATI PVC COATED CONDUIT AND <br /> CONDUIT P/N JAB58H or EQUIVILENT BE BENT 90' TO THEA VERTICAL ON FITTING. <br /> TERMINNATDE WITH AUIT LL <br /> CORD GRIP © CLASSI, DIV II SEAL-OFF FITTING, THREADED ELBOW AND <br /> �_ CONDUIT GROUND LINES TO ® POMECO/OPW 6110-08WT 8" H-20 RATED CORD GRIP FITTING. A BRONZE PIPE CLAMP SHALL 6E ' <br /> #8 GROUND CONNECTED TO THE RISER PIPE TO THE BONDING OR <br /> TERMINATE 2" ABOVE CONDUCTOR CONDUCTOR PENETRATION OTHER SUMPS ACCESS COVER GROUND CONDUCTOR. TO ASSUREACOMPLETE <br /> ABOVE HIGHEST FITTING it �1E CONNECTION, ANY PAINT OR COATING ON THE RISER <br /> PIPE GROUND 11 =1L SHALL BE REMOVED PRIOR TO INSTALLATION OF THE <br /> PENETRATION FITTING CLAMP �_ - -II-� ® 4" NPT ADJUSTABLE BRONZE PIPE CLAMP, <br /> _ II GROUND CLAMP. <br /> CRIMPED F7 LIND EQUIPMENT P/N JR-150-30 (905) 475-5086 <br /> 314" PVC COATED GROUND LUG II -�- - ELECTRICAL CONDUIT, FUELING SYSTEM HARDWARE OR <br /> CONDUIT w/SHORT BOLTED TO HOUSING -II - m ® 3/4" CONDULET ELBOW, CLASS 1 , DIV 1 , THE STATION ELECTRICAL GROUNDING SYSTEM SHALL <br /> RADIUS SWEEP ( ) T��- -��LT NOT BE USED FOR GROUNDING OR BONDING RLL AND <br /> NOT TO SCALE TANK _)T 11r7 - GROUP D, CROUSE-HINDS P/N LBY25OR VAPOR RISERS. <br /> 3/4" WEAVER NOT TO SCALE EQUIVALENT <br /> PENETRATION RISERS INSTALLED ON STEEL UST'S SHALL UTILIZE <br /> FITTINGO GROUND ROD ® 3/4" NPT CORD GRIP, CROUSE-HINDS P/N ISOLATION BUSHINGS PER THE MANUFACTURES <br /> SUMP WALL CGB-292, RANGE .1250 TO .250, ZINC STEEL INSTRUCTIONS TO PREVENT CATHODIC CORROSION. <br /> PENETRATION DETAIL ELEVATION VIEW DETAIL <br /> These drawings and specifications are the confidential and _ APPROVALS <br /> proprietary property of Shell Cil Products US and shall not be Shell Cil Products US o Q G CALIFORNIA U .S.T. STANDARDS <br /> copied, reproduced, disclosed, or used without Shell 011 - DISTRICT MANAGER _ - <br /> Products US written authorization. They are intended as —--"-_-I� [� 1/t/ I I FIBERGLASS <br /> ER I / SS q NKS <br /> contrcct documents for use on this specific project in --" D O `-� U L `� �' I--I- L \ LHJ J �h11 V f\J <br /> j conjunction with its issue date and are not suitable for use on - - Motiva Enterprises LLC AREA TECHNICAL MANAGER r <br /> a different project or at a later date. GRAPHIC SCALE ILL/VAPOR STATIC ELEC PROTECTION <br /> _ TERMINAL MANAGER <br /> 1 10/31 /02 Clarification/Changes jjR 12700 Northborough Drive SCALE: SAP/WIC # DATE: DRAWN: REQUESTED BY: <br /> © Shell Oil Products US. All Rights Reserved 2002 REV DATE DESCRIPTION OF REVISION BY APP Houston TX 77067-2508 ENGINEER <br /> NONE 800062 20 AUGUST 2002 RABAGO HOVLAND EO 1030600-8 <br />