Laserfiche WebLink
GENERAL, TANK INSTALLATION NOTES <br /> 1" FUEL OIL SUPPLY <br /> & 1 1/2' FUEL OIL RETURN 1. ALL UNUSED TANK OPENINGS SHALL BE TIGHTLY SECURED WITH PIPE PLUGS AND SHALL BE COVERED WITH A FIBERGLASS CAP <br /> (HAT) INSTALLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS UTILIZING WET RESIN. ANNUALR TO BE AT FILL END (LOW <br /> 21 END) OF TANK. <br /> 2. ALL TANK RISERS TO BE FACTORY SCOTCH COAT 1206N FUSION BONDED EPDXY COATED SCH. 40 BLACK STEEL PIPE. FIELD <br /> 5 15 12 PATCH ALL EXPOSED OR DAMAGED AREAS & ITITINGS WITH SCOTCH /312 COATING. (MATERIAL SUPPLER: FLETCHER COATING CO. <br /> FOR MULTIPLE QUANTITY OF TANKS: 714/637-4763. ALL VERTICAL. RISER THREADS SHALL BE WRAPPED IN F18ERGIASS 3' MIN. ABOVE EXPOSED THREADS IN <br /> HOLD THIS DIMENSION NOTE: ALL FILL BOXES NUMBER TANKS W/3' BRASS ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. <br /> TO ASSURE (5) GALLON TO BE INSTALLED ON NUMBERS SET IN CONCRETE 3. TANKS SHALL BE TESTED AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AS WELL AS LOCAL <br /> CAPACITY OF SPILL CEIMLNE OF TANK / ADJACENT TO FILL BOX ORDINANCES. <br /> COLLECTOR \ 4. ALL CONTAINMENT BOX ASSEMBLES SHALL BE FIBERGLASSED TO TANK RING AND MUST BE HYDROSTATIC TESTED. <br /> ' 4 5. TANKS TO SLOPE DOWN TOWARD FILL END AND ANNULAR SPACE SENSOR 1/2' MIN., 2' MAX., MEASURED OVER THE LENGTH <br /> 2• SCH. 40 BUCK STEEL OF TANK. USE TRANSIT TO DETERMINE SLOPE. <br /> PRIMARY & 3' FIBERGLASS 6. ALL CONDUITS TO HAVE SEAL-OFFS PER LATEST EDITION OF THE NATIONAL ELECTRIC CODE ALL J--BOXES TO BE EXPLOSION <br /> - - - - SECONDARY VENT PROOF. KILARK 4GRSS-20R CROUSE-HINDS GAA SERIES. ORIENT ALL J-DOXES SUCH THAT THE SCREW LID IS ACCESSIBLE <br /> WITHIN THE FILL BOX OR CONTAINMENT SUMP. <br /> 13 <br /> 7. ALL PENETRATIONS OF THE SUMP BOXES TO BE SEALED BY THE APPROPRIATE SIZE WESTERN FIBDN=1dCC GROMMET OR <br /> N PLAN VIEW SHOWS SUGGESTED PIPING AMERICAN LINING COMPRESSION FITTING. <br /> � <br /> c+ of Y0 1' BALL ORIENTATION. IN ELEVATION VIEW B. USE CABLE CONNECTOR FIRINGS (CROUSE-HINDS CG B OR EQUIVALENT) AT MONITOR & LEVEL GAUGE CABLE CONNECTIONS TO <br /> OVALVE BELOW, SOME PIPING HAS BEEN DELETED J-BOXES & PIPE FITTINGS IN SUMP BOXES. <br /> FOR CLARITY 9. ALL UNDERGROUND CONDUITS AND CONDUITS INSTALLED OUTDOORS TO BE PVC COATED RIGID. ALL CONDUITS INSTALLED INSIDE <br /> BUILDING MAY BE EMT. ALL CONDUIT FTITINGS TO BE COMPRESSION TYPE <br /> 21 NOTE: 10. PRIMARY & SECONDARY PIPING FOR VENT LINE TO BE SCH. 40 SCOTCH COATED BLACK STEEL (PRI.) & AMERON DUOLOY <br /> ORIENT 12• ACCESS OPENING IN HOA OB 30ODL FIBERGLASS (SEC.). REDUCING BOOT IN CONTAINMENT SUMP TO HAVE TEST PORT. <br /> 3 4 OVER SUMP SENSOR J-80X. 11. UNDERGROUND PRIMARY AND SECONDARY PIPING FOR FUEL OIL SUPPLY & RETURN LINES TO BE WESTERN FIB . <br /> SUMP SENSOR MUST BE ABLE TO BULKHEAD REDUCERS IN CONTAINMENT SUMPS, PIPING VAULTS & TRENCHES TO HAVE TEST PORTS. <br /> PLAN VIEW BE EASILY REMOVED VERTICALLY. 12. ALL CONCRETE TO BE 6 SACK MIX, 2500 PSI (MIN.) AT 28 DAYS. <br /> 13. ALL PIPING TO SLOPE DOWN TO UNDERGROUND TANK 1/8" TO 1/4' PER FOOT MIN. <br /> 14. ALL EQUIPMENT, HARDWARE AND SYSTEM COMPONENTS MUST BE INSTALLED IN STRICT CONFORMANCE WITH MANUFACTURER'S <br /> INSTRUCTIONS AND SPECIFICATIONS. <br /> 15. INSTALL PRODUCT TAG IN FILL BOX, ATTACHED TO RISER. <br /> LM�ACQ <br /> GAUGE PROBE RISER MAINTAIN SLOPE AWAY FROM ALL MANWAY <br /> COVERS 3' IN V OR TO EDGE OF SLAB <br /> (WHICHEVER IS CLOSER) SUCTION SYSTEM MATERIAL LIST <br /> TOP OF LID TO <br /> SET FILL BOX TO ALLOW ACCESS 9 22 (rm.) /--� -. <br /> TOP EDGE OF 76 22 fi 8 5 17 110,000 GALLON DOUBLE WALL STEEL, FIBERGLASS COATED COMPOSITE TANK. MODERN WELDING, ENNRO 16. <br /> J-BOX UD FOR LIQUID SENSOORR 11 7 8 5 10 ADAPTOR }U.� <br /> z <br /> MAINTENANCE 2 TANK & PIPING LEAK MONITOR/ELECTRONIC PRODUCT LEVEL GAUGE CONTROL BOX WITH GAUGE PROBE & 3 SENSORS. ALL <br /> N •v /4 O 12' O.C. BOTH WAYS PROBES USED SHOULD BE FOR LIQUID DETECTION. VEEDER-ROOT fU-350 PLUS WITH PRINTER. <br /> DOUBLE POPPET FOOT VALVE & EXTRACTOR ASSY. DPW 486 & 233E-4040 OR EMCO A43 - - <br /> 1 1/2' 9 Ops AND A677 003. <br /> g ° 4 VENT LINE 4*xex2. 150} MALLEABLE IRON EXTRACTOR FTTDNG WITH PLUG UNIVERSAL V420-0020. <br /> \/\\j 5 (2) PIECE CONTAINMENT SUMP Ill FIBERGLASS KIT PHIL-TITE lFG-4261-S-2. SUMPS TO BE INSTALLED BY PHIL-TITS <br /> � <br /> ENTERPRISES USING CHOP GUN (554-223-7400). <br /> BACKFILL LEVEL WATERTIGHT SUMP <br /> SHIELD ADAPTOR (TYP.) _', 4 %\ \/ 16 1 360 DIA. MANHOLE WITH ONE 13• ACCESS COVER PHIL-TRE (TC 3600-OAO.}{ <br /> z 1/2• THREADED PVC <br /> CAP, HAND-TIGHT U <br /> 1s <br /> La <br /> ONLY 3/4' C. 3/4• C. 7 36' DIA. SPILL CONTAINMENT MANHOLE WITH 5 GALLON SPILL BUCKET. PHIL-TTTE ASC-3600-SCA-2, <br /> Nom' <br /> SLOPE SIDES OF TANK m <br /> OB WATERTIGHT SUMP SHIELD ASSEMBLY PHIL- FG-W3-WTSS 4WTC <br /> INCLUDES: -1300. WTR-1013. WTC-8000 & <br /> og 1• p. -�-� <br /> m TO LEAK MONITOR/LEVEL - I HOLE OR USE SHORING WTR-0- .808, INSTALL PER MFR. INSTATLATION INSTRUCTIONS. <br /> a FOR ALL TANK EXCAVATIONS <br /> �g GAUGE CONTROL PANEL I IN ACCORDANCE WITH CAL/OSHA O 4' CAM ADAPTOR WITH IdOSRISON BROS._305CU CAP. <br /> (AFTER BUILDING PENETRATION, RISER FROM TANK 3 CONSTRUCTION SAFETY ORDERS. <br /> q 3/4' CONDUIT MAY BE USED _ 19 12 10 CONDUIT PENETRATION-SEALING GROMMET. AMERICAN LINING COMPRESSION FTG. OR WESTERN FIBERGLASS. (MUST WTHSTAND <br /> Tn 13 <br /> CONCRETE SLAB MUSE NOTE; FOR OPTIMUM INSTALLATION HYDROSTATIC TESTING). <br /> EXTEND 12" PAST I I RESULTS MANUFACTURER SUGGESTS 2 1/2' PLUG IN UNUSED 11 18' DIA X 12' SKIRT LOCKABLE & WATERTIGHT FILL BOX. PHIL-TIE tM1600. <br /> EXCAVATION PERIMETER 2 1/2' SCH. 40 USING ONLY FACTORY THREADED ANNULAR$ ALL AROUND SCOTCH COATED -" I I NIPPLE RISERS ANN12 THREADED TYPE BULKHEAD FITTING AND REDUCING BOOT WITH TEST PORT. AVER DR-3. 2.4. <br /> 2 BLACK STEEL PIPEZZ: SEE NOTE (1) <br /> .3 13 2' x 24• FEMALE x MALE SWIVEL STAINLESS BRAD FLEX CONNECTOR TGEFLCX 110165-32-0240. <br /> 9 " ffi I I - - - - - - - - - - I I ®' � 14 2• CLAY AND BAILEY STEEL DROP TUBE FIELD CUT, a AT BOTTOM. <br /> 794380-208 SENSOR 2 I LUG 794380-208 FILTER FABRIC (WHEN REQ'D 15 RETURN LINE 4'4'2' 150 MALLEABLE IRON EXTRACTOR FffTING OPW REVISIONS AUTHORIZATIONS <br /> 6 (SUMP LOW POINt) I I I SUMPSENSOR 2 I {233-4420 <br /> (SUMP LOW POINT) WITH UNSTABLE SOIL AND/ <br /> I I OR HIGH WATER TABLEi6 EXTRACTOR CAP MORRISON BROS, 4578. NO. Rnlsla+s / AUTNORI7ADDNS DATE V <br /> C I I I I CONDITIONS) 17 VENT CAP IMPACT SAFE SOLUTIONS TANK BREATHER IT60MU. ISSUED FOR BID 11/0/011 MED <br /> F 18 1 1/2' SCH. 40 18 <br /> OVERFILL VALVE, CLAY AND BAILEY F35. ISSUED FOR CONSTRUCTION 3/7/02 MED <br /> BLACKSTEEL PIPE 19 UNIVERSAL SENSOR MOUNTING KIT, VEEDER-ROOT 0330020-01 <br /> B I 20 UL LISTED BALL VALVE TO MATCH PIPE SIZE <br /> I I I 7 PROPRIETARY SBC INFORMATION <br /> oU <br /> 21 PIPE BUSHING 150/ MALLEABLE IRON. F'� �Z NOT FOR GENERAL USE OR DISCLOSURE OUTSIDE OF SBC <br /> I `/ '� caazl9 z�) ENVIRONMENTAL MANAGEMENT UNDER EXEMPTIONS FORTH IN <br /> 22 PHIL-TITE VACUUM TEST FITTING. m THE CALIFORNIA PUBLIC RECORDS ACT. THIS INFORMAMA TION MAY <br /> F" tzsloS a"'! ONLY BE USED BY AUTHORIZED PERSONNEL OF THE LOCAL <br /> GOVERNMENT AGENCY IN CONNECTION WITH APPLICATION FOR <br /> �1 uccAu�'^P�'f PER ITS AND AUTHORIZATIONS FOR BUILDINGS, CONSTRUCTION, <br /> 8 \ 14 b AND OR ZONING CHANGES. <br /> _�� DRAWINGS PREPARED FOR <br /> WESTE <br /> IASS <br /> ITEM NUMBRN FIBER DESCRIPTIO MATERIAL LISA NUM ET <br /> DESCRIPTION <br /> II ENVIRONMENTAL MANAGEMENT <br /> N CASES WHERE A REFURBISHED TANK \\ 847390-10X' <br /> IS USED, THE ABOVE FILL BOX DETAIL \\ 45 2 PRODUCT LEVEL �/ ` (A-1 EXTERIOR OF SUMP WALL 7 (A-2 INSIDE OF ENCLOSURE) PACIFIC REGION <br /> W AND ASSOCIATED NOTES BELOW TAKE \\ \ PROBE 7/ II _� P14526 4' PIPE SECONDARY CONTAINMENT AC8490 REDUCER FITTING 4.9"1PRQIECf TIRE <br /> E PRECEDENCE \\ I `/ P14500 IS' O-P13500 1" FUEL OIL CO-FLEX <br /> AC8486 REDUCER FITTING 6.]x4.5' <br /> b AG6437 PENETRATION B5•x4.5• W/FLANGE PACIFIC BELL FACILITY <br /> ���� P146n BOOT REDUCER 5•x4.5" 10 EAST 12TH STREET <br /> PLUG UNUSED TANK ANNULUS SENSOR II - - P13570 PIPE END FEMALE SWIVEL 1" <br /> i E PORE WITH 2-1/2' SOLD SQUARE \ LL. s ® ® ® ® m ® _ lI_/I P13600 1•x MALE x M.I.P. ADPT. <br /> a HEAD PLUG. (SEE NOTE 1) - - - - - - - - - - - (A-1 INTERIOR OF SUMP WALL) TRACY, CALIFORNIA <br /> _ . <br /> - - - AC8437 PENETRATION B5'x4.5'F W/ FLANGE P14580C PIPE END MALE NON <br /> g - - SLOPE TANK DOWN TOWARD FILL END P14677 BOOT REDUCER 5'1 SM. 1.5' W/ CLAMPS TRACC11 UE058 <br /> $j \ 794390-420 <br /> `\ 2 LEAK SENSOR 1/2' MIN., 2' MAX. MEASURED OVER DEADMAN NOT SHOWN FOR CLARITY AC8490 REDUCER FITTING 4.9'1.4• .9• <br /> SHEET TRTML LENGTH OF THE TANK x7AC8415 PENETRATION B2"x,75F <br /> (A-2 OUTSIDE OF SUMP WALL7 EMERGENCY GENERATOR SUCTION SYSTEM <br /> AC8411 PENETRATION B2"1' <br /> P14526 4' PIPE SECONDARY CONTAINMENT <br /> � (_ P135M 1• FUEL OIL PIPE TANK SECTION/SLAB PLAN <br /> P74500 1.5' CO-FLEX PIPE DATE 03/07/02 SCAT AS NOTED <br /> -III- ESDNATE/ RANINE ORDER <br /> 12' SOILCLEAN, WASHED AC84B8 REDUCER FITTING 8.7'x4.5' <br /> o: COMPACTED SAND BED UE1354E DRAWN � B1: MED <br /> SPT CHECKED MED <br /> a AND BACKFILL sec AUIHORIunoN: <br /> ��[ji ARC®IBCIOR6 • IiNGQi®tIIIG • @IV@OI7�NIAL 3®iVEC115 SHEET: 3 OF: 8 SHEETS LSHEETNO,G I ����-+ 1137 N. tacDOWELL BLVD. PETALUMA, CA 94954 (707) 765-1660 SBC DRAWING NO.:1 TYPICAL TANK PRODUCT SUCTION SYSYTEM SCALE: NONE elm I a.� mJON W JOHNSON, ARCHITECT JAMES H. RAY, DHL ENGINEER TRAC11 -01 -0111 <br />