Laserfiche WebLink
r 4 <br /> 5 . ) Water Not Present In Tank Pit : <br /> Tank Size ( A ) 0 to 1 , 000 gallons a minimum of one soil <br /> samples will be taken from either the pump <br /> or the fill end of -the tank , below bottom of <br /> tank . <br /> ( a) 1 ,001 to lO , QOO a minimum of two soil samples <br /> will be taken . One sample from each end of <br /> the tank, , below bottom of tank . <br /> (C ) 10 , 001 and up a minimum of three soil samples <br /> will be taken spaced evenly alone the length <br /> of the tank , below bottom of tank . <br /> 5 . ) Water is Present in Tank Pit : <br /> Tank Size ( A ) 10, 000 gallons or less ( single tank) the <br /> minimum number of soil samples will be <br /> two from the tank wall at each end of <br /> soil/ground water interface . The minimur7 <br /> number of water samples shall be one . <br /> ( S) 10 , 001 and larger tank , or a cluster of <br /> tanks the minimum number of soil samples <br /> to be taken shall be four , one from each <br /> wall at soil/ground water interface . A <br /> minimum of one water sample shall be taken . <br /> CHEMICAL SECTION :. <br /> 1 . ) ContentE, of Tank : <br /> Diesel Fuel <br /> 2 . ) Residual : Triple rinse by I,Torth Cal Construction. <br /> Residual to be pumped out and disposed of by Refinery <br /> Services <br /> 3 . ) Authorization 1.... " �. 11 <br /> Soil analyees authorization form attach t <br />