Laserfiche WebLink
,`,�. r <br /> SAN JOAQUI N LOC-A,I- HF-12 . rH DI =al CT <br /> SAMPLING PRO`I'OCAL FOR ROUTINE TANK REMOVALS <br /> The following represents minimum sain ling criterion required for closure compliance. If <br /> contamination is documented during closure, an Unauthorized Release notification must be <br /> filled out and submitted to SJLHD within 5 days. Section 2652, CCR. <br /> WATER NOT PRESENT IN THE TANK PIT <br /> { — TANK SIZE MINIMUM NUMBER OF LOCATION OF SOIL SAMPLES ! <br /> _ SOIL SAMPLES <br /> (Less than 1000 gallons ONE per tank Fill or pump end of tank <br /> 1000- 7--10 _QQO al Ions f <br /> ____g ( TWO per tank <br /> 10,001 gallons and up THREE OR MORE Ends and Middle or <br /> per 'tank � generally spaced along <br /> Piping ONE EVERY 20 LINEAL FEET <br /> N TANK PIT <br /> TANK SIZE MINIMUM NO. OF LOCATION OF SOIL MINIMUM NUMBER <br /> SOIL SAMPLES SAMPLES OF WATER SAMPLEq <br /> 10,L00 GALLONS From wall next toOR � <br /> tank ends at soil/i <br /> (Single Tank) TWO groundwaterI ONE <br /> interface <br /> GREATER THAN From wall nextto ONE <br /> 10,00oRGALLONS tank ends at soil/ <br /> groundwater <br /> TANK CLUSTER FOUR interface <br /> e <br /> I <br />