ITTS Integrity Tank Testing Systems, Inc. <br /> December 3 , 1991 <br /> °Fc i1 <br /> 1991 <br /> Mr. Ed Stockton <br /> SITHE ENERGIES USA, INC. <br /> 2526 West Washington <br /> Stockton, California 95203 <br /> Dear Mr. Stockton: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheets, graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested . <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK $ OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Northwest 11000 .waste Oil - .0211 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />