PRESSURE VACUUM VENT 12" 72" 1" GALVANIZED VENT PIPING MIN. SLOPE "
<br /> CAPS (SEE NOTE BELOW) TO VENTS 1/8" PER FOOT, MAX
<br /> LENGTH. MAX. DISTANCE WITHOUT
<br /> PIPE
<br /> PRESSURE VACUUM VENT CAP FLOAT CHECK VALVE SUPPORT NOT TO EXCEED 10', ® '
<br /> (SEE NOTE BELOW) DISTANCES OVER 10' REQUIRE PRIOR SAME ELEV. AS
<br /> P/N 9468G APPROVAL OF BP DESIGN MANAGER. TOP OF P V VALVE
<br /> OVEFILL PROTECTION
<br /> 2" GALVANIZED ARCO UNION & NIPPLES 1AIR 2' MINIMUM ABOVE ASSEMBLY
<br /> MRADE /N 9948 ARCS
<br /> 2"X1" REDUCER BUSHING 1" BLADDER
<br /> SYPHON RP WEST COAST PRODUCTS,LLC
<br /> VAPOR INLET ASSM. AWANCE MANAGER, AGENT FOR EP:
<br /> P/N 9956 (REF.)
<br /> 2" GALVANIZED ELBOW
<br /> SYPHON TUBE ADAPTER
<br /> P/N 9934 (REF.) Bovis
<br /> FASTEN VENT RISER TO FRAME W/
<br /> 3/8"0 HOLE BOLT LOCK W/ _ � Lend Lease
<br /> WASHER HEX NUT (NP.)
<br /> G/oba/Alliance
<br /> \ HEALY CLEAN AIR SEPARATOR KIT 4CENTERPOINTEORIVE
<br /> INCLUDES CLEAN AIR SEPARATOR TANK, LA PALMA,CA 9M
<br /> BALL VALVE BALL VALVES, FLOAT CHECK, REDUCER NAnoxa SM ADAPT CONSULTANT:
<br /> LOCKED OPEN BUSHINGS AND ALL ACCESORIES SHOWN
<br /> MANUFACTURER SUPPLIED OR � EXCEPT 1" PIPING.
<br /> MOUNTING TUBING IN NORMAL
<br /> OPERATION '
<br /> BALL VALVE P/N 996123 II z G E s
<br /> 3 LOCK P/N 996124 HEALY CLEAN AIR SEPARATOR
<br /> o USE KEY P N 996725 V I VAPOR J
<br /> w I (36" O.D. X 93" L.G.)
<br /> CO BALL VALVE go
<br /> LOCKED OPEN I I I P/N 9961
<br /> s z 2" SCH. 40 GALV. STEEL OR
<br /> o VENT RISER PAINT TO 14 SYPHON TUBE N 3 o
<br /> Q� a MATCH SITE CONDITIONS IN NORMAL I P/N 4186-6 (REF.) . $�N
<br /> OPERATION
<br /> BALL VALVE P/N 996123 ' � �a AT
<br /> LOCK P/N 996124 §
<br /> `r USE KEY P/N 996125
<br /> w
<br /> h BALL VALVE \I R '
<br /> LOCKED OPEN �/ o
<br /> OR CL
<br /> T II
<br /> 2" TEE WITH 1/4" TEST IN NORMAL \ 400 GALLON BLADDER, NO. DATE REMSION OESCRIPnON
<br /> PORT FITTING AND 1/4" OPERATION I I P/N 9943 (REF.) Qi
<br /> PLUG (TYP.) BALL VALVE P/N 996123
<br /> LOCK P/N 996124 Zz
<br /> USE KEY P/N 996125 ' (NP. 4 PLCS.)
<br /> HOOP BOLLARD
<br /> 2" SCH. 40 GALVANIZED STEEL RISER. 4
<br /> PAINT PER SPECS (TYP.) EXPLOSION PROOF J-BOX
<br /> MOUNTED TO POST ( 'I ae
<br /> 2" OPENINGS I NOTE: 0
<br /> IT TEE WITH 1/4" TEST PORT COMPRESSION PASS FRONT VIEW OF BOLLARD
<br /> FITTING AND 1/4" PLUG (TYP.) SEAL OFF /
<br /> THRU (TYP.) NOT SHOWN IN THIS VIEW
<br /> FOR CLARITY. SEE PLAN
<br /> EXPLOSION PROOF J-BOX INSTALL ROPE R 1" CONDUIT W/ PULL �I
<br /> MOUNTED TO POST DAGNOSTIIICFR REQUIREMENTS ROUTE I VIEW BELOW
<br /> TO MONITORING PANEL IN BUILDING Io
<br /> SEAL OFF \ \\ TT
<br /> EXPLOSION PROOF J-BOX
<br /> MOUNTED TO POST PLUG
<br /> RACK FOUNDATION TO BE O SEAL'
<br /> ENCASED IN CONCRETE O SEAL OFF _
<br /> USE (4) 1/2"z4 3/4" HILTI KWIK
<br /> 3" TO 2" TERMINATION
<br /> FITTING W/ TEST PORT GRADE BOLT OR EQUAL ICBG ESR 1385
<br /> (TYP.) 4 9 G;
<br /> 2" INSIDE 3" DOUBLE �� �\ %j��/ X " ° d. ° ° NOTE 044785 z v
<br /> WALL FRP VENT LINE. / /� s ' , s ' , PBr EXP.3-31-2008 $
<br /> SEE NOTE BELOW. /�/��� I /��/�� V' CONDENSATE HEBE LOCATED AN CONFORMANCE WITH
<br /> TANK O `Prq,,f CIV1Y.oF,�a�/
<br /> 7\� \�
<br /> DRAIN MANUFACTURERS INSTALLATION MANUAL,1�1
<br /> CARS EXECUTIVE ORDER VR-201-A AND
<br /> gI s • s 6" CONC. SLAB W/#4 , e , < ALL APPLICABLE STATE AND LOCAL
<br /> 8 Um BARS ® 18' O.C. E/W O°� ' S(,D►
<br /> 2" FLEX CONNECTOR TO INTRINSICALLY SAFE ° s e e CODES. PER CFC 2001 SECTION CaNROExnu Tr STATEu�n
<br /> 2" FLEX CONNECTOR (TYP.) WIREWAY IN BUILDING 5202.13.3.2 & 5202.13.3.3
<br /> ( > (TYP.) FRONT ELEVATION NOTE: TME"EOPIENTOETHESE TORIA.E1..L WERETARA.
<br /> C M31T M 1EPW515 OWYED 9 TA ^ 0 K50.
<br /> Mi PECPV i C EES TO RETPW MESE RP S iR
<br /> 3" ENTRY BOOT TYP. DOUBLE WALL VENT s s m AEE"u e s 1FSRP1""PPAP1 POO`�ANI c .rxcty.
<br /> CONSTRUCTION MAY BE REQUIRED BY O I R POW A �E ORCES
<br /> ( -- - - LINE TRANSITION SUMP e e ADDITIONAL SCREEN WALL OR °AGREES NOT Too . SSE
<br /> SENS[ POST ENS nor i°"AVE c PTEs or m RA AVS ME Ec nE".
<br /> SEr✓slrl vF S£NSSk (SINGLE WALL SUMP) LOCAL ORDINANCES. MINIMUM MOUNTING ^c°EEG T°°EE TME M^,ER„-s a„E*ERR TME uMMO
<br /> 2" INSIDE 3" DOUBLE WALL •� .p d, d vRR,'R O'E'S R>xs MAGE ra unreRlnEs
<br /> REQUIREMENTS ARE SHOWN IN THIS ASIS.wm MEc,a,11 AGREES TO REnRN Au
<br /> FRP PENT LINE. SLOPE TO un"rtERlas TO eR E@EER uv°v aMPmrcN w IRE
<br /> 2" BELLxMALE ADAPTER , s , s .� A DETAIL. PER CFC 2001 SECTION reR.Ru¢POSE.0.TME Rw11EST OF RP.
<br /> DOUBLE WALL VENT TANK AT 1/8" PER FOOT a " a , +a¢"EVER OWES iIRS,.
<br /> 5202.13.3.2
<br /> LINE TRANSITION SUMP MINIMUM. SEE NOTE BELOW.
<br /> (SINGLE WALL SUMP) FRONT ELEVATION 4'-0" 1'-2" 5202.13.3.2 LOCATION DEVELOPMENT iNFORMATKIN:VAPOR-PROCESSING EQUIPMENT SHALL BE LOCATED AT OR
<br /> 1'-0 71/16" (TYP.) ABOVE GRADE. SOURCES OF IGNITION SHALL BE LOCATED NOT
<br /> 11 LESS THAN 50 FEET (15240mm) FROM FUEL-TRANSFER
<br /> AREAS AND NOT LESS THAN 18 INCHES (457.2mm) ABOVE
<br /> SIDE ELEVATIONVENT PIPING MOUNTING RACK TANK FILL OPENINGS AND TOPS OF DISPENSER ISLANDS.
<br /> - e
<br /> -� VAPOR-PROCESSING UNITS SHALL BE LOCATED NOT LESS
<br /> THAN 10 FEET (3048mm) FROM THE NEAREST BUILDING OR
<br /> PROPERTY LINE OF A PROPERTY WHICH CAN BE BUILT UPON.
<br /> HOOP BOLLARD A0
<br /> EXCEPTION: WHERE THE REQUIRED DISTANCES TO 91E ADDRESS
<br /> (TYP. 4 PLCS.) mi BUILDINGS, PROPERTY LINES OR FUEL-TRANSFER AREAS
<br /> CANNOT BE OBTAINED, MEANS SHALL BE PROVIDED TO 130 S. WILSON WAY
<br /> PROTECT EQUIPMENT AGAINST FIRE EXPOSURE. ACCEPTABLE
<br /> MEANS INCLUDE:
<br /> NOTES, 2" FLEX CONNECTOR 1. APPROVED PROTECTIVE ENCLOSURES, WHICH EXTEND AT STOCKTON,CA,
<br /> IN ORDER TO PROVIDE MECHANICAL FLEXIBILITY WITHIN THE RIGID PIPING SYSTEM, PROVIDE AT LEAST (TYp-) LIQUID SENSOR o LEASE 18 INCHES (457.2mm) ABOVE THE EQUIPMENT, --
<br /> 4 FEET OF STRAIGHT PIPE RUN BEFORE A CHANGE IN DIRECTION. OF 30 DEGREES OR MORE. (NFPA NON-DISCRIMINATING a CONSTRUCTED OF FIRE-RESISTANT OR NON-COMBUSTIBLE #05469
<br /> 30A (2000 & 2003) §5.3.3(2)), (UFC (2000) $7901.11.7.2) MATERIALS OR
<br /> EXPLOSION PROOF J-BOX 2. RE PROTECTION USING AN APPROVED WATER-SPRAY pypm ew CB yEl, �� --
<br /> THE VENT CONFIGURATION SHOWN IS IN ACCORDANCE WITH CP-201 THE NUMBER OF VENT CAPS AT MOUNTED TO POST SYSTEM
<br /> ANY GDF SHALL NOT PERMIT AN ADDITIVE LEAK RATE OF MORE THAN .17 CHF AT 2" OF WATERa�aDD er. SIRREPM: -
<br /> COLUMN. MAX ALLOWED WITHOUT MANIFOLDING IS (3). SINGLE WALL VENT LINE 30" DIA. VAPOR-PROCESSING EQUIPMENT SHALL BE LOCATED A CB
<br /> 2" BELLzMALE ADAPTER BASE OIUMN St ALLIANCE PIE
<br /> THE VENT DISCHARGE SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE POINT OUTSIDE TRANSITION SUMP O o MINIMUM OF 20 FEET (6096mm) FROM DISPENSING DEVICES. BL
<br /> OF BUILDINGS AND NOT LESS THAN 3.6 M (12 FT) ABOVE THE ADJACENT GROUND LEVEL. VAPORS (TYP.) 1v PROCESSING EQUIPMENT SHALL BE PROTECTED AGAINST VERSION: PROACT Na
<br /> SHALL BE DISCHARGED UPWARD OR HORIZONTALLY AWAY FROM ADJACENT WALLS. VENT OUTLETS SHALL 3"x2" CONTAINMENT PHYSICAL DAMAGE BY GUARDRAILS, CURBS, PROTECTIVE AR2264
<br /> BE LOCATED SO THAT VAPORS WILL NOT BE TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL TERMINATION FITTING W/ 11/16" DIA. ENCLOSURES OR FENCING, WHEN APPROVED PROTECTIVE
<br /> ENCLOSURES ARE USED, APPROVED MEANS SHALL BE
<br /> WITH
<br /> PROVIDED TO VENTILATE THE VOLUME WITHIN THE ENCLOSURE DRAWnnE:
<br /> AT LEAST 1.5 M (5 FT ) FROM BUILDING OPENINGS, VENTS SHALL BE INSTALLED IN ACCORDANCE TEST PORT ('TYP.) 4 HOLES ON
<br /> WITH (NFPA 30 (2003) §5.7.2), (UFC (2000) §7902.73). 32" DIA. B.C, TO PREVENT POCKETING OF FLAMMABLE VAPORS. VENT STACK
<br /> VENT RISERS SHOULD STAND NO LESS THAN 3' FROM OUTSIDE EDGE OF CURB 3" DOUBLE ENTRY IF A DOWNSLOPE EXISTS TOWARD THE LOCATION OF THE INSTALLATION DETAILS
<br /> THE ACTUAL NUMBER OF VENT RISERS IS DETERMINED BY THE NUMBER OF UNDERGROUND B00T (TYP.) 2'-0" 2,-0„ VAPOR-PROCESSING UNIT FROM A FUEL-TRANSFER AREA, W/HEALY CLEAN AIR SEPARATOR
<br /> STORAGE TANKS, THE DIESEL VENT RISER (IF INSTALLED) IS ALWAYS SEPERATE.
<br /> THE CHIEF IS AUTHORIZED TO REQUIRE ADDITIONAL
<br /> SEPARATION BY DISTANCE AND HEIGHT. -Si EST NO:
<br /> 2" INSIDE 3" DOUBLE 5202.13.3.3 INSTALLATION
<br /> WALL FRP VENT LINES VAPOR-PROCESSING UNITS SHALL BE SECURELY MOUNTED ON
<br /> CONCRETE, MASONRY OR STRUCTURAL STEEL SUPPORTS ON ,o,6.A
<br /> CONCRETE OR OTHER NON—COMBUSTIBLE FOUNDATIONS. V L
<br /> PLAN VIEW PLAN VIEW VAPOR-RECOVERY AND VAPGR-PROCESSING EQUIPMENT IS
<br /> -- ALLOWED TO BE INSTALLED ON ROOFS WHEN APPROVED.