Laserfiche WebLink
OUTPUT RELAY SETUP - - - <br /> T 3:DIESEL LEAK TEST METHOD <br /> PRODUCT CODE 3j - - - - - - - - - - - - R 1 :REGULAR SOUTH 10K <br /> THERMAL COEFF : .000450 TEST ANNUALLY: ALL TANK TYPE: <br /> TANK DIAMETER 120.00 JAN WEEK 1 MON STANDARD <br /> TANK PROFILE 20 PTS START TIME : 12:00 AM NORMALLY CLOSED <br /> FULL VOL 5001 TEST RATE :0.20 GAL/HR <br /> 114.0 INCH VOL 4905 DURATION 4 HOURS LIQUID SENSOR ALMS <br /> 108.0 INCH VOL : 4737 L 2:FUEL ALARM <br /> 102.0 INCH VOL 4526 :FUEL ALARM <br /> L 5 <br /> 96.0 INCH VOL : 4284 L 5:FUEL ALARM <br /> 90.0 INCH VOL 4018 L 7:FUEL ALARM <br /> 84.0 INCH VOL 3734 L 8:FUEL ALARM <br /> 78.0 INCH VOL : 3436 L 2:SENSOR OUT ALARM <br /> 72.0 INCH VOL 3129 <br /> 66.0 INCH VOL : 2814 L 5:SENSOR OUT ALARM <br /> 60.0 INCH VOL 2497 L 6:SENSOR OUT ALARM <br /> L 7:SENSOR OUT ALARM <br /> 54.0 INCH VOL : 2179 L 8:SENSOR OUT ALARM <br /> 48.0 INCH VOL : 1865 <br /> 42.0 INCH VOL : 1557 L 2:SHORT ALARM <br /> 36.0 INCH VOL : 1260 L 5:SHORT ALARM <br /> 30.0 INCH VOL : 976 L 6:SHORT ALARM <br /> 24.0 INCH VOL : 711 L 7:SHORT ALARM <br /> 18.0 INCH VOL : 470 LIQUID SENSOR SETUP I L B:SHORT ALARM <br /> 12.0 INCH VOL : 260 - - _ _ - - - - - - - _ <br /> 6.0 INCH VOL : 93 R 2:REG MIDDLE 5K <br /> L 1 :ANNULAR TYPE: <br /> TRI-STATE STANDARD <br /> FLOAT SIZE: 4.0 INCHES CATEGORY : ANNULAR SPACE NORMALLY CLOSED <br /> WATER WARNING 1 .5 LIQUID SENSOR ALMS <br /> HIGH WATER LIMIT: 1 .5 L 3:FUEL ALARM <br /> L 2:REGULAR SOUTH 10K L 5:FUEL ALARM <br /> L 6:FUEL ALARM <br /> MAX OR LABEL VOL: 5001 TRI-STATE <br /> OVERFILL LIMIT 90k7:FUEL ALARM <br /> 4500 CATEGORY : STP SUMP L 6:FUEL ALARM <br /> HIGH LEVEL LIMIT: 95/ L 3:SENSOR OUT ALARM <br /> 4750L 5:SENSOR OUT ALARM <br /> L 3:REGULRR MIDDLE 5K <br /> DELIVERY LIMIT 250 TRI-STATE L 7:SENSOR OUT:SENSOR OUT ALARM <br /> CATEGORY : STP SUMP I L 8:SENSOR OUT ALARM <br /> LOW LEVEL LIMIT 250L 3:SHORT ALARM <br /> LEAK ALARM LIMIT: 50 L 4:DIESEL L 5:SHORT ALARM <br /> SUDDEN LOSS LIMIT: 50 TRI-STATE L 6:SHORT ALARM <br /> TANK TILT 0.00 CATEGORY : STP SUMP L B: SHORT ALARM <br /> :SHORT ALARM <br /> MANIFOLDED TANKS <br /> T#: NONETRI-STATE3-4 R 3:DIESEL <br /> TYPE: <br /> LEAK MIN ANNUAL 500 CATEGORY <br /> DISPENSER PANSTANDARD <br /> NORMALLY CLOSED <br /> PERIODIC TEST TYPE <br /> STANDARD LIQUID SENSOR ALMS <br /> L 6:DISP 1-2 L 4:FUEL ALARM <br /> ANNUAL TEST FAIL TRI-STATE L 5:FUEL ALARM <br /> L 6:FUEL ALARM <br /> ALARM DISABLED CATEGORY : DISPENSER PAN <br /> L 7:FUEL ALARM <br /> PERIODIC TEST <br /> AALARM <br /> ALARMDISA13LED L 4:SENSOROUT ALARM <br /> L 7:DISP 7-8 L 5:SENSOR OUT ALARM <br /> GROSS TEST FAIL TRI-STATE L 6:SENSOR OUT ALARM <br /> L 7:SENSOR OUT ALARM <br /> ALARM DISABLED CATEGORY : DISPENSER PAN L B:SENSOR OUT ALARM <br /> ANN TEST AVERAGING: OFF ', L 4:SHORT ALARM <br /> PER TEST AVERAGING: OFF L 5:SHORT ALARM <br /> L 8:DISP 5-6 I L 6:SHORT ALARM <br /> TANK TEST NOTIFY: OFF TRI-STATE L 7:SHORT ALARM <br /> TNK TST SIPHON BREAKOFF CATEGORY : DISPENSER PAN L 8:SHORT ALARM <br /> R 4: <br /> DELIVERY DELAY 5 MIN TYPE: <br /> STANDARD <br /> NORMALLY OPEN <br /> III - NO ALARM ASSIGNMENTS - <br />