Laserfiche WebLink
t <br /> ITISIntegrity Tank Testing Systems, Inc. <br /> August 22 , 1991 <br /> Mr. Aldo Freggi aro, jr. <br /> PORT OF STOCKTON [B � g <br /> P. O. Bok 2089 <br /> Stockton, California 95201 fWIRONMEN1A-"Y4�1 <br /> Site. Cardlock <br /> PE1tM�j 1 S�,RVIC�S <br /> 2201 West Washington <br /> Stockton, California <br /> Dear Mr. Freggiaro <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheets, graphs, anti/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested. <br /> A tank systeri may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred.,, and <br /> you should consider taking remedial action, <br /> TANK #$ OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 12 , 000 U/L Gas - .005 Yea <br /> West 12 , 000 Diesel +. 011 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Since ely, <br /> W. N. Savage SFCS r1��� r.r, <br /> Certified Tester u -= <br /> 1 pOR Of' v 1991 ,I-! <br /> ' �`�Ar10 O�j <br /> OP to <br /> cKr <br /> NS <br /> 800 262-8378 166 Frank west Circle Stockton, CA 95206 (209) 466-8036 <br />