Integrity Inc. <br /> IT c, <br /> FEB 24. 1993 <br /> ENVIRONMENTAL HEALTH Au gu s t 14 , 1990 <br /> PERMIT1SERVIOES <br /> Mr. Aldo Freggiaro, Jr. <br /> PORT OF STOCKTON <br /> P. 0. Box 2089 Site: Cardl.ock <br /> Stockton, California 95201 2201 West Washington <br /> Dear Mr. Freggiaro: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets, graphs, and <br /> computer generated data for your submittal to the <br /> appropriate governmental agency. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 12 , 000 U/L Gas - .025 yes <br /> West 12 , 000 Diesel -. 033 yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, ,. <br /> rank J. K s r <br /> Certified ster <br /> o�ti <br /> 800 262-8378 166 Funk West Circle Stockton, CA 95206 -8036 <br />