Laserfiche WebLink
PORT OF STOCKTON <br /> NW OF PORT RDS B&2 <br /> ALDO FEGGIANO 209 946-0246 <br /> TANK TESTER VER 2.01 <br /> FUEL TYPE: GASOLINE (GEAR ROOM 2) <br /> CAPACITY TANK 1 : 605 GALLONS <br /> TEMPERATURE COEFFICIENT: 668 ppm/deg F <br /> TEST CRITERIA: +0.000 GPH TO +0.000 GPH <br /> 04/12191 TEST TIME FROM 11: 13 TO 12:20 <br /> DATA ANALYSIS INDICATES: <br /> A GROSS VOLUME CHANGE OF: +0.000 GALLONS <br /> A VOLUME CHANGE DUE TO TEMPERATURE OF: -0.000 GALLONS <br /> A LIQUID VOLUME RATE OF CHANGE OF: +0.001 GPH <br /> WITH A 99 7 CONFIDENCE INTERVAL OF: +1-0.000 GPH <br /> (+0.002 TO +0.001 GPH) <br /> V. _� <br /> TESTER. ,U. . . . . . , . . . . . . <br /> CUSTOMER. . . . . . . . . . . . . . <br /> ti I <br /> l <br />