Laserfiche WebLink
r <br /> ITTSIntegrity Tank Testing Systems, Inc. <br /> e <br /> TEST DATA AND <br /> TEST RESULTS <br /> ApriZ 20, 2988 <br /> -Mr. Mike Trent <br /> Port of Stockton Site. NE of Port Roads G & 14 <br /> Stockton, California <br /> P. 0. Box 2089 <br /> Stockton, CaZifornia 95201 = <br /> Y Dear Mr. Trent: <br /> F'ollowitrg is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the-'test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 20, 000 DieseZ - . 026875 Yes <br /> South 20, 000 DieseZ - . 03325 Yes <br /> Please contact us if you nee-! additional assistance or <br /> information. <br /> Sincerely , <br /> W. Savage <br /> Certified Tester <br /> 800 262-8378 166 FYank West Circle Stockton, CA 95206 (209) 466-8036 <br />