Laserfiche WebLink
0 0 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Shell Oil 12-29-03 <br /> 1071 N.Main Street—Manteca,CA.95336 <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ❑O Industry Standard I7 Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑x Hydrostatic <br /> ❑ Other(Specify) <br /> Equipment Resolution: <br /> Test Equipment Used: Measuring tape Example " increments <br /> Spill Box # 87 Spill Box# 91 Spill Box#Waste Oil Spill Box# <br /> Bucket Capacity in gallons: 15 5 15 5 10 <br /> Bucket Depth: 1 6 '/x" 11 '/z" 1'6" 11" 1'1" <br /> Wait time between filling with 5 min 5 min 5 min 5 min 5 min <br /> water and starting test: <br /> Test Start Time: 8:30 am 8:30 am 8:35 am 8:35 am 8:40 am <br /> hritial Reading(Rj): 6" 4 '/d' 5 '/d' 5'/a" 21/2" <br /> Test End Time: 9:30 am 9:30 am 9:35 am 9:35 am 9:40 am <br /> Final Reading(RF): 6" 4 %" 5 '/ 5'/d' 21/2" <br /> Test Duration: 1 hour I hour 1 hour I hour 1 hour <br /> Change in Reading(Rr-Rj): None None None None None <br /> Pass/Fail Threshold or Criteria: ZERO LOSS ZERO LOSS ZERO LOSS <br /> Test Result: 0 Pass ❑D Pass 0 Pass <br /> Comments — (include information on repairs made prior to testing and recommendedfollow-upforfailed tests) <br /> All Buckets Passed. <br />