Laserfiche WebLink
TANKNOLOGY - UNDERG,ROUN EAP: DETECTION SYSTEM Page. 21 <br /> ULTRAMAR #474 HdM7-IVE340537-83482-03 Jul 15, 1993,108:36 <br /> TEST DATE Jul 15, 19':43 <br /> START TIME 09: 36: 51' <br /> CLIENT ULTRAMAR <br /> LOCATION NAME ULTRAMAR #474 <br /> LOCATION CODE 474 <br /> I <br /> TANK: CONFIGURATION : Single <br /> TANK CONTENTS RUN <br /> TANK NUMBER : 03 <br /> TANK DIAMETER 95 in <br /> TANK CAPACITY 10000 G <br /> TANK MANUFACTURER <br /> TANK MATERIAL Steel <br /> TANK REGISTRATION # <br /> TANK DATE INSTALLED <br /> INITIAL DIP'P'ED FUEL LEVEL : 85. 00 in <br /> INITIAL DIPPED WATER LEVEL : 0. 00 in <br /> POST PUMPING WATER LEVEL : 0. 00 in <br /> 1 A N11<: TE---SST 1---e EE E3 U -F <br /> TEST INITIAL WATER LEVEL : 0. 00 in <br /> TEST FINAL WATER LEVEL : 0. 00 in <br /> WATER INGRESS 0. 00 in <br /> BUBBLE SIGNATURES : No <br /> VAC:U-TELT TEST RESULT Passed <br /> COMMENTS: <br /> CONCLUSION. TANK #3 TIGHT <br /> L- I N11_ T E'E3-I- Fl"E:Ei U L-F <br /> TEST FATE <br /> LINE RESULT PRESSURE OF' LOSS <br /> #1 Passed 50 PSI i3Oo GPIs <br /> #2 <br /> #y3 <br /> #`Y <br /> #5 <br /> #6, <br /> COMMENTS: <br /> CONCLUSION: LINE #3A TIGHT <br /> This test was conducted in accordance with U.B. EPA Rule 40 CFR Parts 280 and 281. <br /> HOU93O7-IVE340537-83482-03 <br /> BEAN LUKEHART VACU-TECT(tm) Test Number <br />