Laserfiche WebLink
INVOICE #WC000142 <br />0 0 <br />USTest 2000 / P <br />CHAMPION PRECISION TANK TESTING <br />P.O. BOX 13059 <br />SACRAMENTO, CALIF, 95813-3059 <br />TANK STATUS EVALUATION REPORT <br />***** CUSTOMER DATA ***** <br />STOCKTON FUEL INC. <br />4075 EAST MAIN ST. <br />STOCKTON,CA. <br />95206 <br />CONTACT: JAY McILRATH <br />PHONE #: 209-462-8707 <br />TEST DATE: 03/19/95 <br />***** SITE DATA ***** <br />JAMAR EXXON <br />4075 EAST MAIN ST. <br />STOCKTON,CA. <br />95206 <br />CONTACT: STORE MANAGER <br />PHONE #: 209-462-8707 <br />***** COMMENT LINES ***** <br />CURRENT EPA STANDARDS DICTATE <br />THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br />OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br />TANK #1: REG UNLEADED TYPE: STEEL RATE: .028246 G.P.H. GAIN <br />TANK IS TIGHT. <br />TANK #2: PLUS UNLEADED TYPE: STEEL <br />TANK IS TIGHT. <br />TANK #3: SUPER UNLEADED TYPE: STEEL <br />TANK IS TIGHT. <br />RATE: .004475 G.P.H. GAIN <br />RATE: .003865 G.P.H. GAIN <br />OPERATOR:, \ w� SIGNATURE: \\-_--- 37 DATE: <br />----�- <br />- -� 7-1 I G- Pi <br />