Laserfiche WebLink
F i • <br /> INVOICE #WC000163 TEST DATE: 04/15/95 <br /> USTest 2000 / P <br /> CHAMPION PRECISION TANK TESTING <br /> P.O. BOX 13059 <br /> SACRAMENTO, CALIF, 95813-3059 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> STOCKTON EAST WATER DISTRICT STOCKTON EAST WATER DISTRICT <br /> P.O.BOX 5157 P.O.BOX 5157 <br /> 6767 EAST MAIN ST. 6767 EAST MAIN ST. <br /> STOCKTON,CA. STOCKTON,CA. <br /> 95205 95205 <br /> CONTACT: RICHARD BERMUDEZ CONTACT: RICHARD BERMUDEZ <br /> PHONE #: 209-948-0537 PHONE #: 209-948-0537 <br /> ***** COMMENT LINES ***** <br /> TANK # 1 IS THE NORTH TANK <br /> TANK # 2 IS THE SOUTH TANK <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br /> TANK #1: REG UNLEADED TYPE: RATE: .028836 G.P.H. LOSS <br /> TANK IS TIGHT. <br /> TANK #2: REG UNLEADED TYPE: RATE: .031705 G.P.H. GAIN <br /> TANK IS TIGHT. <br /> OPERATOR: ►il !A SIGNATURE:`�� -� DATE: <br />