Laserfiche WebLink
IT T S Integrity Tank Testing Systems,*mM. <br /> TEST DATA AND <br /> TEST RESULTS <br /> Mr. Dave Silva <br /> Silva Trucking <br /> 2119 West Alpine Site: 36 West Matthews Road . <br /> Stockton, California 95204 French Camp, California <br /> Dear Mr. Silva: <br /> Following is a summary of the precision testing we recently conducted on <br /> your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and computer generated data <br /> for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight, according to the current rules, if the <br /> loss or gain is less than .OS gallons per one hour of testing. If the results <br /> are beyond these parameters, you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESUL'T'S TANK PARAMETERS <br /> Shop 12,000 Diesel +.038 Yes <br /> Please contact us if you need additional assistance or information. <br /> Sincerely, <br /> an Kese <br /> Certified ster <br /> 800 262-8378 166 Frcmk West Circle Stockton, CA 95206 (209) 466-8036 <br />