Laserfiche WebLink
Test Site: PENSKE TRUCK LEE UG <br /> LINE TEST DATA <br /> Line Test Method Used: NDE PTK-88 <br /> Test Date: 11-03-95 11-03-95 <br /> Tank Number: T 1 East T 2 West <br /> Product: Diesel Unlead <br /> Pump Type: Turbine Turbine <br /> Pump Make: Red Jacket Red Jacket <br /> Isolator: None None <br /> Line Material: DW DW <br /> Line Diameter (inches): 2 2 <br /> Test Pressure (psi): 50 50 <br /> Test Time (minutes): 10 10 <br /> Finish PSI: 49.5 50 <br /> Volume change (ml): 2 0 <br /> Volume change (GPH): 0.003 0 <br /> Pass/Fat PASS PASS <br /> Line Test Comments: None. <br /> LEAK DETECTOR DATA <br /> Test Method used: Red Jacket Approved AVO (Apparatus to Verity Operation) in accordance with EPA 40CFR280.44(a)per RJ-21 <br /> Test Date: 11-03-95 11-0395 <br /> Tank Number: T 1 East T 2 West <br /> Product: Diesel Unlead <br /> Manufacturer: <br /> Leak Detector Model: <br /> Serial Number: <br /> Resiliency (ml): <br /> Opening Time (minutes): <br /> Test Leak Rate (ml/min): <br /> Metering PSI: <br /> Restricted Flow: <br /> Pass/Fal: <br /> Leak Detector Coimments: Red Jacket Leak Detectors not yet instated. <br /> PYoTanF,In¢ -3545 Lomita Boulevard, Suite 6-Torrance, CA 90505(31 OI 681-0470 <br />