Laserfiche WebLink
SAN JOAQU I N LOCAL HE AT_TH DISTRICT <br />The following represents minimum sampling criterion required for closure compliance. If <br />contamination is documented during closure, an Unauthorized Release notification must be <br />filled out and submitted to SJLHD within 5 days. Section 2652, OCR. <br />WATER <br />NOT PRESENT IN THE <br />TANK PIT <br />TANK SIZE <br />MINIMUM NUMBER OF <br />LOCATION OF SOIL SAMPLES <br />SOIL SAMPLES <br />Less than 1000 gallons <br />ONE per tank <br />Fill or pump end of tank <br />1000 - 10,000 gallons <br />TWO per tank <br />One at each end of tank <br />10,001 gallons and up <br />THREE OR MORE <br />Ends and Middle or <br />per tankgenerally <br />spaced along <br />the length of the tank <br />Piping <br />ONE <br />EVERY 20 LINEAL FEET <br />WATER IS FRES M IN TANK <br />PIT <br />TANK SIZE MINIMUM NO. OF LOCATION <br />OF SOIL MINIMUM NUMBER <br />SOIL <br />SAMPLES SAMPLES OF WATER SAMPLES <br />10,000 GALLONS <br />From wall <br />next to <br />OR LESS <br />tank ends <br />at soil/ <br />(Single Tank) <br />TWO groundwater ONE <br />interface <br />GREATER THAN <br />From wall <br />next to ONE <br />10,000 GALLONS <br />tank ends <br />at soil/ <br />ORoundwater <br />TANK CLUSTER <br />FOUR interface <br />