Laserfiche WebLink
b. 'll monitoring probe inputs shall be Belden 8448 if length of <br /> equals 0 to 1,000 ft. If length of run equals 1,000 to <br /> 2,500 ft. , Belden 9182 cable shall be used. <br /> c• W�.auxiliary input wire shall be 18 gauge, TIM, shielded <br /> d. Auxiliary output wire shall be of sufficient size and type to <br /> allow for proper operation of end devices. <br /> 4. Horn - An audible horn shall be furnished, installed and tested . <br /> with all necessary wire and terminations for a complete, operas <br /> system located ing <br /> at grids A-5 in the warehbuse. A `silence button, <br /> which automatically resets when the alarm condition clears shall <br /> be located at grids A-5 in the warehouse. <br /> The horn shall be a Federal Vibratone Horn, Model 450, 24 VDC, WB <br /> housing, grey, surface mounted or approved alternate. The <br /> location shall be as designated on the drawings. All wire shall <br /> be run in conduit. <br /> 5. Light - A small 24 VDC red LED type indicating light shall be <br /> provided to indicate an alarm condition. This light shall <br /> automatically extinguish upon the clearance of the alarm condition <br /> and shall not be affected by the silence button. <br /> Nom: The light and silence button shall be mounted in the tank <br /> monitor panel cover so as to be readily visible. <br /> N. Tank sand piping installation shall be supervised by the tank manufac- <br /> turer's representative and monitoring equipment installation and <br /> start-up shall be by the monitoring equipment manufacturer's author- <br /> ized service representative. <br />