Laserfiche WebLink
'il41 IV I'11-1i 14 I`IP-1141 C L.t.1, L.1-1 a.�a.:ru iww.. .1 uu_u.c: ....�... .0 uyi w1 •-,., .•..+ <br /> 71-FE C_"r `1--1' S3-1- 81_ 1 rvt A k:Y <br /> TEST DATE : Apr 23, 1992 <br /> START TIME : 00: 533: 56 <br /> CLIENT : ULTRAMAR <br /> LOCATION NAME 47i> N MAIN MANTECA, CA 95336 <br /> LOCATION CODE <br /> TANK CONFIGURATION Tandem <br /> TANK CONTENT'S SUN/ PLUS <br /> TANK NUMBER : I,3 04 <br /> TANK' DIAMETER : '35 95 in <br /> TANS: CAPACITY 10000 10000 G <br /> TANK MANUFACTURER <br /> TANK: MATERIAL Steel Steel <br /> TANK REGISTRATION # <br /> TANK. DATE INSTALLED <br /> INITIAL DIPPED FUEL LEVEL : 73. 00 73. 00 in <br /> INITIAL DIPPED WATER LEVEL : 0. 10 0. 00 in <br /> POST PUMPING WATER LEVEL : O. 00 0. 00 in <br /> TEST INITIAL WATER LEVEL : 0. 00 0. 00 in <br /> TEST FINAL WATER LEVEL O. O0 0. 00 in <br /> WATER INGRESS 0. 00 0. 00 in <br /> BUBBLE SIGNATURES No No <br /> VACU-TEC:T TEST RESULT : Passed Passed <br /> COMMENTS: <br /> C:ONC:LUSION: TANKS 1 , 2 TESTED TIGHT <br /> l� .0 INN "r EZE:3"1- <br /> TEST RATE TEST RATE <br /> LINE RESULT PRF_SSUFuE OF LOSS N-,ESULI PRESSURE OF LOSS <br /> #1 Passed 50 PSI 0. 00 GPH Passed 50 PSI 0. 00 GPH <br /> #2 Passed 50 PSI 0. Oo GPH Passed 50 PSI 0. 00 GPH <br /> #J <br /> #4 <br /> #5 <br /> #6 <br /> 1 <br /> COMMENTS: <br /> I CONCLUSION: LINES 1, 2 TESTED TIGHT. <br /> This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 280 and 281. <br /> HOU9204-ITB896129-52327-03 <br /> KEN REYNOLDS VACU--TECT(tm) Test Numbei <br /> TANKNOLOGY - UNDERGROUND LEAK. DETECTION SYSTEM - (V3. 12) Page 1 <br />