Y •� <br /> PERFORMED BY SACRAMENTO EQUIPMENT MAINTENANCE COMPANY} INC. <br /> 2533 CONNIE DRIVE - SACRAMENTO - CALIFORNIA - 95815 <br /> PHONE 916-925-2716 <br /> WORK ORDER # 58218 DATE <br /> SITE NUMBERS 3/492 PRODUCT F�r'rsJlA� <br /> SITE NAME: Beacon STP BRAND <br /> SITE ADDRESS: 407 N. Main Street <br /> Manteca , CA <br /> RED JACKET LEAK, DETECTOR TEST <br /> PRODUCT:(P. UNLEADED, PREMIUM-UNLEADED, DIESEL (CIRCLE ONE) <br /> NOTE: USE SEPARATE FORM FOR EACH TAN):. <br /> 1) RUNNING PRESSURE 3(j <br /> 2) SHUT-OFF PRESSURE c <br /> 3) AMOUNT OF PRODUCT RELEASED THRU BIBCOCK TO ZERO. OZ. <br /> 4) WITH VALVE OPEN, START STP. LIS PRESSURE PSI. <br /> 5) REDUCE FLOW TO RATE OF 7 OZ. PER MINUTE. <br /> LIST PRESSURE AT THIS FLOW RATE PSI. <br /> 6) TURN STP OFF. LET PRESSURE DROP TO ZERO THRU LEAK JUST <br /> CREATED. LIST TIME FOR GAUGE TO REACH ZERO. MIN.=-.YD SEC. <br /> 7) TURN THE STP RAC ON. KEEP LEAK, RATE AT BISCOCK� <br /> LIST PRESSURE PSI. FLOW RATE AT NOZZLE GPM. <br /> 8) STOP LEAK WITH STP STILL ON. <br /> DOES LEAK DETECTOR RESET? L/S'�ES NO <br /> IF YES, HOW LONG TO RESET? MIN. SEC. <br /> 9) TURN STOP OFF. LIST PRESSURES PSI. <br /> 10) TURN STP BACK, ON. <br /> LIST TIME TO REACH PRESSURE RISE. MIN. �_ SEC. <br /> 11) LIST PRESSURE � PSI. <br /> 12) OPEN NOZZLE AND LIST PRESSURE c�ad PSI. <br /> 13) SATISFACTORY LEAK DETECTOR 2- YES NO. <br /> THIS TEST IS FOR LEAK DETECTOR SERIAL # ([[8-t <br /> LEAF; DETECTOR <br /> (OLD) MODEL DATE CODE & SERIAL NUMBER <br /> (NEW) MODEL DATE CODE & SERIAL NUMBER <br />