Laserfiche WebLink
`���1��1�7��1��7�tl��CDK1l��tl�E�il��►l�tlfJ(�i�f�►t9�E����i1��{t�il��il�nClll�����f�{i�l�� <br /> CERTIFICATE OFWDERGROUND STORAGE TANWSTEM TESTING <br /> AMNOLOGY-NDE TANKNOLOGY-NDE <br /> I 8900 SHOAL CREEK, BUILDING 200 <br /> AUSTIN, TEXAS 78757 <br /> (512)451-6334 <br /> FAX (512)459-1459 <br /> TEST RESULT SITE SUMMARY REPORT <br /> TEST TYPE: VPLT <br /> TEST DATE: 04/15/97 WORK ORDER NUMBER: 2201047 <br /> CLIENT: ULTRAMAR INC SITE: ULTRAMAR 492 <br /> 525 W THIRD ST 470 N MAIN ST <br /> HANFORD, CA 93230 MANTECA, CA 95336 <br /> ATTN: SANDY HUFF <br /> The following test were conducted at the site above in accordance with all applicable portions of Federal,NFPA and local regulations <br /> Tank Tests <br /> TANK TANK TANK VOLUME <br /> PRODUCT CAPACITY TANK ULLAGE <br /> NUMBER DIAMETER RESULTS CHANGE RESULT <br /> (Gallons) (Inches) (gphI <br /> 87 UNLEADED 9,929 94.00 PASS —0.016 PASS <br /> 92 SUPER 9,929 93.00 PASS —0.006 PASS <br /> 89 PLUS 9,929 93.00 PASS —0.014 PASS <br /> Line and Leak Detector Tests <br /> TANK VOLUME CHANGE LINE RESULT LEAK LEAK <br /> NUMBER PRODUCT (gph) (P=pass,F=fail DETECTOR DETECTOR <br /> 1=inconclusive) <br /> A.... 6. C D A 8 C D PRESENT RESULT <br /> [92 <br /> 7 UNLEADED 0.006 P YES PASS <br /> SUPER 0.007 P YES PASS <br /> 9 PLUS 0.005 P YES PASS <br /> TANKNOLOGY-NDE appreciates the opportunity to serve you,and looks foward to working with you in the future.Please call any time,day or <br /> night,when you need us. <br /> TANKNOLOGY-NDE Representative: Test conducted by: <br /> MARK SHAW MICHAEL T LEVESQUE <br /> Reviewed. Technician Certification Number: <br />