Laserfiche WebLink
INDIVIDU*ANK/LINE/LEAK DETECTOR TE kREPORT NDE <br /> NDE ENVIRONMENTAL CORPORATION „ <br /> TEST DATE: April 17, 1996 WORK ORDER NUMBER: 965862 <br /> CLIENT. ULTRAMAR INC SITE: ULTRAMAR 492 <br /> TANK INFORMATION <br /> Tank : 89 <br /> Product: PLUS Bottom to top fill in inches: 120.0 <br /> Bottom to grade fill in inches: 127.o <br /> Capacity in gallons: 9,929 Fill pipe length in inches: 27.0 <br /> Diameter in inches: 93.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 344 <br /> Stage lvapor recovery: COAX <br /> STEEL <br /> Material: <br /> Tank: NO Stage II vapor recovery: ASSIST <br /> Manifolded Vent: YES <br /> V/R: No <br /> COMMENTS <br /> TANK TEST RESULTS LEAK.DETECTOR RESULTS <br /> Test method: Alert 1000 <br /> Psi at tank bottom: 1.82 New/passed Failed/replaced Fluid level in inches: 67.75 detector detector <br /> UFT/OFT: UFT Test method: FTA <br /> Fluid volume in gallons: 7,753 Make: RED JACKET <br /> Water level in inches: 0.00 Model: FX <br /> Test time: 23:18-01:55 S/N: 0322955624 <br /> Number of thermisters: Open time in sec: 3.00 <br /> Specific gravity: 0.748 Holding psi: 13 <br /> Water table depth in inches: 300.00 Resiliency cc: 110 <br /> Determined by(method): NONTR WELL Test leak rate ml/min: 189.0 <br /> Leak rate in gph: -0.026 Metering psi: 3.0 <br /> RESULT: PASS Calib. leak in gph: 3.00 <br /> RESULT: PASS <br /> COMMENTS COMMENTS.- <br /> ULLAGE TEST RESULTS LINE TEST RESULTS" <br /> Test method: Alert 1050 <br /> Test time: 02:24-02:34 Material: FIBERGLASS <br /> Ullage volume: 2,176 Diameter(in): 2.0 <br /> Ullage pressure: 1.50 Length (ft): 40.0 <br /> RESULT: PASS Test psi: 50 <br /> Bleedback cc: 100 <br /> DATA FOR UTS-4T ONLY: Test time(min): 30 <br /> Time of test 1: Test 1:start time: 00:07 <br /> finish psi: so <br /> Temperature: vol change cc: 5 <br /> Flow rate (cfh): Test 2:start time: 00:17 <br /> Time of test 2: finish psi: 50 <br /> vol change cc: 0 <br /> Temperature: Test 3:start time: 00:27 <br /> Flow rate(cfh): finish psi: 50 <br /> Time of test 3: vol change cc: 0 <br /> Temperature: Final gph: 0.003 <br /> Flow rate (cfh): RESULT: PASS <br /> Test type:AcuRite <br /> COMMENTS Pump type: PRESSURE Pump make: RED JACKET <br /> -... COMMENTS <br /> 8906 WALL STREET SUITE 306 AUSTIN TEXAS 78754 512 719-4633 <br />