Laserfiche WebLink
IND IVIDU ANK/LINE/LEAK DETECTOR TEO REPORT NDE <br /> NDE ENVIRONMENTAL CORPORATION SM <br /> TEST DATE: May 25, 1995 WORK ORDER NUMBER: 964191 <br /> CLIENT: ULTRANAR INC SITE: ULTRANAR 492 <br /> TANK INFOAMATION <br /> Tank ID: 1 Bottom to top fill in inches: 122.0 <br /> Product: REG UNLEAD Bottom to grade fill in inches: 132.0 <br /> Capacity in gallons: 10,000 Fill pipe length in inches: 28.0 <br /> Diameter in inches: 94.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 337 Stage I vapor recovery: COAX <br /> Material; STEEL <br /> Tank: No Stage II vapor recovery: ASSIST <br /> Manifolded Vent: YES <br /> V/R: No <br /> COMMENTS <br /> TANKTESTRESULTS LEAK DETECTOR RESULTS <br /> Test method: New/passed Failed/replaced <br /> Psi at tank bottom: detector detector <br /> Fluid level in inches: <br /> UFT/OFT: Test method: FTA Fluid volume in Model: FX Make: RED JACKET <br /> gallons: <br /> Water level n inches: S/N: 0322955622 <br /> Test time: Open time in sec: 3.00 <br /> Specific gra <br /> Number of thermravityty:: Holding psi: 14 <br /> Resiliency cc: 110 <br /> Water table depth in inches: <br /> Determined by (method): Test leak rate ml/min: 189.0 Leak rate in gph; Metering psi: 10 <br /> Calib. leak in gph: 3.00 3.00 <br /> RESULT: RESULT: PASS PASS <br /> -':COMMENTS COMMENTS. <br /> REPLACED FAILED LD DLD 109906086 <br /> ULLAGE TEST RESULTS UNE TEST RESULTS <br /> Test method: <br /> Test time: Material: FIBERGLASS <br /> Ullage volume: Diameter(in): 2.0 <br /> Ullage pressure: Length (ft): 40.0 <br /> RESULT: Test psi: <br /> Bleedback cc: <br /> DATA FOR UTS-4T ONLY: Test time(min): <br /> Time of test 1: Test 1:start time: <br /> finish psi: <br /> Temperature: vol change cc: <br /> Flow rate (cfh): Test 2:sten time: <br /> Time of test 2: finish psi: <br /> vol change cc: <br /> Temperature: Test 3:start time: <br /> Flow rate (cfh): finish psi: <br /> Time of test 3: vol change cc: <br /> Temperature: Final gph: <br /> Flow rate (cfh): RESULT: <br /> Test type: <br /> 'COMMENTS Pump type: PREssDRE Pump make: RED JACKET <br /> -. COMMENTS <br /> 8906 WALL STREET SUITE 306 AUSTIN,TEXAS 78754 512 719-4633 <br />